Inspections for the day of: Wednesday, April 18, 2018.
Number of inspections: 25
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC17-01076 Mec-Aging Inspection4/18/20184/18/20184/19/2018 3:27:46 PM PEND
contractor to schedule final per phone call
MEC18-01717 Final4/17/20184/18/20184/18/2018 4:09:05 PMPPASS
Call Eric to coordinate @ 412.6613 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- furnace ac coil co ok
MEC18-01717 Pressure Test4/17/20184/18/20184/18/2018 4:07:56 PMPPASS
Call Eric to coordinate @ 412.6613 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- 5lb flue pass
MEC18-01680 Final4/16/20184/18/20184/18/2018 3:52:39 PMPPASS
INSTALLER JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace ac coil co ok
MEC18-01680 Pressure Test4/18/20184/18/20184/18/2018 3:52:21 PMPPASS
INSTALLER JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- 5lb flue pass
MEC18-01727 Final4/18/20184/18/20184/18/2018 3:05:07 PMPNH
Inspection requested via web by MARGIE ROWE- no one home no access- need permit for new electrical to outdoor heat pump ?
MEC18-01703 Rough-in4/18/20184/18/20184/18/2018 2:23:06 PMPPASS
Phone #: ###-#### Inspection requested via web by Devony Bullard- R/I ok
MEC18-01703 Pressure Test4/18/20184/18/20184/18/2018 2:17:28 PMPPASS
Phone #: ###-#### Inspection requested via web by Devony Bullard- 20lb gas pass
MEC18-01647 Rough-in4/18/20184/18/20184/18/2018 1:29:46 PMPPART
meet at 115 pm with Dave-2083918945- part R/I inspection on hard lids- ok to cover hard lids only
MEC18-01448 Rough-in4/17/20184/18/20184/18/2018 11:55:00 AMAPASS
BARBARA ###-#### OR ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace R/I ok
MEC18-01448 Pressure Test4/17/20184/18/20184/18/2018 11:54:29 AMAPASS
BARBARA ###-#### OR ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- 20lb gas pass
MEC18-01707 Pressure Test4/17/20184/18/20184/18/2018 11:15:52 AMAPASS
This building is located at the rear of the cemetery on Dawn road Phone #: ###-#### Inspection requested via web by Joe Taylor- 60lb pass from meter location to both unit heaters
MEC18-00821 Final4/17/20184/18/20184/18/2018 10:51:37 AMAPASS
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- final ok
MEC18-01703 Rough-in4/17/20184/18/20184/18/2018 10:47:19 AMAFAIL
Phone #: ###-#### Inspection requested via web by Devony Bullard- needs insulation sheild in attic on B vent- dryer vent needs to maintain 4" id and cant be ovaled- pressure test was not ready- left correction notice in front window
MEC18-01703 Pressure Test4/17/20184/18/20184/18/2018 10:44:34 AMAFAIL
Phone #: ###-#### Inspection requested via web by Devony Bullard- pressure test wasnt ready
MEC18-00664 Final4/17/20184/18/20184/18/2018 10:26:19 AMAPASS
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- final ok
MEC17-05780 Final4/17/20184/18/20184/18/2018 9:49:46 AMACANC
Phone #: ###-#### Inspection requested via web by Oleg Chervak- scheduled final twice
MEC17-05780 Final4/17/20184/18/20184/18/2018 9:49:11 AMAFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak- unit 102 needs fresh air vent finished- unit 103 needs transfer grille in dryer/washer closet- left correction notice in front window of 102
MEC17-05781 Final4/17/20184/18/20184/18/2018 9:47:45 AMAFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak- unit 104 cracks in drain pan need sealed- left correction notice in front window of 102
MEC18-00249 Rough-in4/17/20184/18/20184/18/2018 9:46:04 AMAPASS
Cover inspection needed for Am on April 18th, 2018. If you have any questions you may contact Karl at ###-#### thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin- seal ok- ok for ceiling tiles
MEC18-01145 Rough-in4/17/20184/18/20184/18/2018 8:44:37 AMAPASS
Phone #: ###-#### Inspection requested via web by Krista Boss- R/I ok
MEC18-01647 Rough-in4/18/20184/18/20184/18/2018 8:27:13 AMACANC
please call me so can meet to walk job Phone #: ###-#### Inspection rescheduled for afternoon per phone call with Dave
MEC17-02368 Mec-Aging Inspection4/18/20184/18/20184/18/2018 8:16:12 AM PEND
contractor will try to schedule final per phone call
MEC17-02360 Mec-Aging Inspection4/18/20184/18/20184/18/2018 8:13:54 AM PEND
contractor will try to schedule final per phone call
MEC17-03612 Final4/17/20184/18/20184/17/2018 3:38:02 PMADONE
Please call brock 1 hr in advance so he can get you access.

We were under the impression that this was inspected last year. if it did not happen lets get you in to look at the work we did. we apologize for the inconvenience. There was some thought that this was through ada county . sorry for the mix up Phone #: ###-#### Inspection requested via web by Nicholas Paige- this address is in the county- its voided out-