Inspections for the day of: Wednesday, April 18, 2018.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-01061 FIRE-Final Inspection4/17/20184/18/20184/18/2018 2:38:34 PMPPASS
No fire sprinkler modifications required, no fire alarm modifications required, fire extinguisher is in common area with a current inspection tag. Final life fire safety inspection for area of work complete.
BLD18-01208 FIRE-Final Inspection4/18/20184/18/20184/18/2018 1:49:53 PMPPASS
No fire sprinkler modifications required, no fire alarm modifications required, fire extinguisher was being mounted at time of inspection, extinguisher has a current inspection tag. Final life fire safety inspection complete.
FIR17-00682 INSP-Sprinkler Rough-in4/17/20184/18/20184/18/2018 1:24:16 PMAPART
Rough to cover inspection for overhead fire sprinkler piping located above new cooler in basement level complete, piping that is above cooler approved for cover.
FIR18-00230 INSP-Final Inspection4/17/20184/18/20184/18/2018 1:23:15 PMAPASS
Final fire alarm inspection for area of work complete.
BLD17-00587 FIRE-Final Inspection4/16/20184/18/20184/18/2018 9:52:10 AMAFAIL
Provide sticker on main east entry reading "Door to remain unlocked while occupied". Provide fire extinguishers with current inspection tags throughout tenant space including mezzanine. Provide emergency lighting to include exit discharge landings and exit signs per city approved drawings (Notated city approved plans with red ink). North exit door in gym area requires panic hardware (Notated city approved plans with red ink). Provide single action door hardware (Notated city approved drawings with red ink the exterior doors requiring single action door hardware). Provide occupant load sign for gym area.