BLD17-01061
| FIRE-Final Inspection | 4/17/2018 | 4/18/2018 | 4/18/2018 2:38:34 PM | P | PASS |
|
|
No fire sprinkler modifications required, no fire alarm modifications required, fire extinguisher is in common area with a current inspection tag. Final life fire safety inspection for area of work complete.
|
BLD18-01208
| FIRE-Final Inspection | 4/18/2018 | 4/18/2018 | 4/18/2018 1:49:53 PM | P | PASS |
|
|
No fire sprinkler modifications required, no fire alarm modifications required, fire extinguisher was being mounted at time of inspection, extinguisher has a current inspection tag. Final life fire safety inspection complete.
|
FIR17-00682
| INSP-Sprinkler Rough-in | 4/17/2018 | 4/18/2018 | 4/18/2018 1:24:16 PM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping located above new cooler in basement level complete, piping that is above cooler approved for cover.
|
FIR18-00230
| INSP-Final Inspection | 4/17/2018 | 4/18/2018 | 4/18/2018 1:23:15 PM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
|
BLD17-00587
| FIRE-Final Inspection | 4/16/2018 | 4/18/2018 | 4/18/2018 9:52:10 AM | A | FAIL |
|
|
Provide sticker on main east entry reading "Door to remain unlocked while occupied". Provide fire extinguishers with current inspection tags throughout tenant space including mezzanine. Provide emergency lighting to include exit discharge landings and exit signs per city approved drawings (Notated city approved plans with red ink). North exit door in gym area requires panic hardware (Notated city approved plans with red ink). Provide single action door hardware (Notated city approved drawings with red ink the exterior doors requiring single action door hardware). Provide occupant load sign for gym area.
|