Inspections for the day of: Friday, April 19, 2002.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD01-03230 FIRE-Final Inspection4/12/20024/19/20024/19/2002 12:00:00 AMAFAIL
wall mounted device are wrong candella, wall listed devices mounted on ceiling. Review comments were not followed. Elevator recalled is wrong. I stopped inspection. Entire inspection needs to be started over. 4/19/2002 12:48:22 PM
BLD02-00678 FIRE-Final Inspection4/19/20024/19/20024/19/2002 12:00:00 AMAPASS
Hood extinguishing system and fire alarm system operated correctly
BLD01-02423 FIRE-Final Inspection4/18/20024/19/20024/19/2002 12:00:00 AMPCANC
inspection cancelled. The two panels in the building weren't connected 4/19/2002 4:24:04 PM