BLD01-03230
| FIRE-Final Inspection | 4/12/2002 | 4/19/2002 | 4/19/2002 12:00:00 AM | A | FAIL |
|
|
wall mounted device are wrong candella, wall listed devices mounted on ceiling. Review comments were not followed. Elevator recalled is wrong. I stopped inspection. Entire inspection needs to be started over. 4/19/2002 12:48:22 PM
|
BLD02-00678
| FIRE-Final Inspection | 4/19/2002 | 4/19/2002 | 4/19/2002 12:00:00 AM | A | PASS |
|
|
Hood extinguishing system and fire alarm system operated correctly
|
BLD01-02423
| FIRE-Final Inspection | 4/18/2002 | 4/19/2002 | 4/19/2002 12:00:00 AM | P | CANC |
|
|
inspection cancelled. The two panels in the building weren't connected 4/19/2002 4:24:04 PM
|