Inspections for the day of: Monday, April 19, 2004.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-02287 FIRE-Sprinkler Rough-in4/16/20044/19/20044/19/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 4/16/2004 at 1:08:55 PM. Contact: ###-####. See sprinkler FIR permit for details 4/19/2004 3:00:36 PM
FIR04-00156 INSP-Final Inspection4/16/20044/19/20044/19/2004 12:00:00 AMAFAIL
We will be there at 8:00am. Ready and Waiting. Jonathan will be on site.; Phone #: ###-#### Internet Inspection Request from: Trent Bice Remote area has changed and will need submittals for calc's; room 6100 is OH and is overspaced; room 6041 is overspaced; room 6018 is overspaced; telephone hallway needs heads installed; evidence room 6109 is OH and is overspaced 4/19/2004 2:59:36 PM
FIR04-00114 INSP-Sprinkler Rough-in/Hydro4/16/20044/19/20044/19/2004 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 4/16/2004 at 3:33:16 PM. Contact: ###-####. thrust blocks installed; main still under water at tie-in to UW main 4/19/2004 2:56:52 PM
FIR02-00005 INSP-Sprinkler Rough-in4/19/20044/19/20044/19/2004 12:00:00 AMPPART
The 2.5 inch line in area D first floor has shifted from plans and branch lines installed per plans; need EQ at west end of 2.5 inch on first floor as it is overspaced from end of pipe; the tie-ins to exsisting mains aren't completed; okay on first floor area C and D - heads/drops not completed 4/19/2004 3:06:57 PM
BLD00-03428 FIRE-Sprinkler Rough-in4/16/20044/19/20044/19/2004 12:00:00 AMPPART
calvin ###-#### See sprinkler FIR for info 4/19/2004 4:07:00 PM