ELE05-00393
| Electrical Rough-In | 4/18/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | A | PASS |
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ric ok 4/19/2005 10:47:51 AM
|
ELE05-01300
| Electrical Rough-In | 4/18/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | A | PASS |
|
|
###-#### HAILEY ric ok 4/19/2005 8:30:09 AM
|
ELE05-01053
| Final | 4/18/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | A | PASS |
|
|
george; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to final. 4/19/2005 9:25:15 AM
|
ELE05-01284
| Temporary Service | 4/18/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | A | PASS |
|
|
CONTACT: MIKE ROBINSON; Phone #: ###-#### Internet Inspection Request from: Deb McCoy t/s u/g n ok 4/19/2005 8:08:06 AM
|
ELE05-00870
| Final | 4/18/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | A | NR |
|
|
Scheduled by a contractor via Hello! on 4/18/2005 at 11:42:52 AM. Contact: ###-####. met with builder and elect and elect just got paper work on design and needs to re-vamp layout on storage room. I said to recall when ready. 4/19/2005 11:38:56 AM
|
ELE05-01230
| Electrical Rough-In | 4/18/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | P | PASS |
|
|
ed; Phone #: ###-#### Internet Inspection Request from: Barbara Moore north walls, bathroom walls and ceiling, and electric room walls ok to cover. nw cubicles to be later on inside of perimeter. 4/19/2005 2:12:11 PM
|
ELE04-03161
| Electrical Rough-In | 4/19/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 4/19/2005 at 8:01:42 AM. outside soffits and classroom wall ok to cover 4/19/2005 4:39:31 PM
|
ELE05-01309
| Temporary Service | 4/19/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | P | PASS |
|
|
clyde ###-#### p/s u/g n ok 4/19/2005 3:02:12 PM
|
ELE05-01310
| Electrical Rough-In | 4/19/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | P | FAIL |
|
|
Call Francis with questions.; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa called contr, left corr notice,300.4(A)(1) and (D) shall provide nailplates and 1 1/4" from inside and outside edges of framing members. 110.14 shall use proper crimping tool and inastallation for ground splicing. Note, check recpt at edge of new and old construction on outside of house 4/19/2005 4:44:20 PM
|
ELE05-01311
| Electrical Rough-In | 4/19/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | P | PASS |
|
|
###-#### - dean ric ok 4/19/2005 12:15:13 PM
|
ELE05-01308
| Electrical Rough-In | 4/19/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | P | PASS |
|
|
tom--for floor insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie floor ok to cover 4/19/2005 12:50:39 PM
|
ELE05-01311
| Permanent Service | 4/19/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | P | PASS |
|
|
p/s u/g n ok
|