FIR04-00748
| INSP-Supply line flush | 4/18/2005 | 4/19/2005 | 4/19/2005 3:43:41 PM | P | PASS |
|
|
Underground fire supply line flush OK.
|
BLD04-02888
| FIRE-Final Inspection | 4/18/2005 | 4/19/2005 | 4/19/2005 2:22:26 PM | A | FAIL |
|
|
Fail life safety inspection. Need current tag on fire extinguisher, install lever hardware on backdoor, install lever hardware on exterior enclosure gate facing Overland Rd., adjust hardware on one interior dog gate. Hardware type and height on three i
|
FIR04-00811
| INSP-Final Inspection | 4/18/2005 | 4/19/2005 | 4/19/2005 10:01:39 AM | A | FAIL |
|
|
2nd floor rough-in fail inspection. Two pendent heads in CEO office are too close to heat diffusers - must be min. one foot away or increase temp. rating. Upright head blocked in open office without ceiling, verify drop ceiling install or correct the
|
BLD04-02877
| BLD-Final | 4/19/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | A | PART |
|
|
Temp. occupancy given per. Dave Lokker, pending fire alarm and fire sprinkler modifications.
|
BLD04-01896
| BLD-Final | 4/19/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | A | PART |
|
|
Temp. occupancy given per. Dave Lokker, pending fire alarm and fire sprinkler modifications.
|
BLD04-02877
| FIRE-Final Inspection | 4/19/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | A | PART |
|
|
Temp. occupancy given per. Dave Lokker, pending fire sprinkler modifications in spray booth and compressor room.
|
BLD04-01896
| FIRE-Final Inspection | 4/19/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | A | PART |
|
|
Temp. occupancy given per. Dave Lokker, pending fire sprinkler modifications in spray booth and compressor room.
|
BLD04-02877
| FIRE-Alarm Testing | 4/19/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | A | PART |
|
|
Temp. occupancy given per. Dave Lokker, pending fire alarm modifications to include addition of three tamper switches and one flow switch addressed to 2990 Wise Way.
|
BLD04-01896
| FIRE-Alarm Testing | 4/19/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | A | PART |
|
|
Temp. occupancy given per. Dave Lokker, pending fire alarm modifications to include addition of three tamper switches and one flow switch addressed to 2990 Wise Way.
|
FIR05-00150
| INSP-Final Inspection | 4/19/2005 | 4/19/2005 | 4/19/2005 12:00:00 AM | P | PASS |
|
|
Fire alarm finaled. Mag door locks operated properly under test conditions.
|