Inspections for the day of: Wednesday, April 19, 2006.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02730 ELE-Aging Inspection4/19/20064/19/20064/20/2006 12:04:37 PM PART
called wsuc
ELE06-00856 Electrical Rough-In4/19/20064/19/20064/19/2006 3:45:54 PMPPART
r/i and conference gate location on orchard met with dave
ELE05-04395 Final4/19/20064/19/20064/19/2006 2:38:44 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: TJ Sturges corr. called 314.16 box fill all boxes island counter, 210.8 needs gfci MB sinks,410.8 install fixture with required clearence or remove all wiring understairs closet, 334.15 protect all exposed wiring, and install conn on all flex both ends island counter, 210.52(A) outlet spacing nupstairs bed rm by window seat/shelves, 406.4 recepts loose in boxes and not flush with plates, panel not labeled correctly schedule does not match branch circuits
ELE06-00309 Final4/19/20064/19/20064/19/2006 1:13:55 PMPPASS
please do a final elect. insp. of the barn. thank you.; Phone #: ###-#### Internet Inspection Request from: William Zerfas ok
ELE06-00314 Permanent Service4/18/20064/19/20064/19/2006 12:26:21 PMAPASS
Permanant Service / House Meter inspection, please call Tom, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters p/s u/g new for house meter ok
ELE06-01337 Electrical Rough-In4/18/20064/19/20064/19/2006 11:36:38 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Clyde Logan corr. called 300.4 nail plates and 11/4"
ELE06-01338 Rough-In Permanent Service4/19/20064/19/20064/19/2006 10:26:42 AMAPASS
charlie Internet Inspection Request from: Melyne Davis r/i ok p/s u/g new ok
ELE06-01335 Temporary Service4/18/20064/19/20064/19/2006 9:47:38 AMAPASS
Daryl -- huge transformer/power pole across street 13960 W Wainwright; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong t/s u/g new ok
ELE06-01141 Permanent Service4/18/20064/19/20064/19/2006 8:51:44 AMAFAIL
Internet Inspection Request from: Tyler Bowen corrections not made and new violations created, 110.26(F)(2) remove bush for p/s clearence, 110.12(A) seal all unused KOs, 240.24(A) breaker spaces over 6ft7" 408.4 label panel, 314.16 box fill new jbox in basement under stairs, 250.104(A)(1) bond hot and cold called fee due posted also