BLD04-01323
| FIRE-Final Inspection | 4/19/2006 | 4/19/2006 | 4/20/2006 9:22:45 AM | P | NR |
|
|
Project related fire alarm is not finaled.
|
FIR05-00075
| INSP-Final Inspection | 4/18/2006 | 4/19/2006 | 4/20/2006 8:19:28 AM | P | DEFR |
|
|
Scheduled by a contractor via Hello! on 4/18/2006 at 3:35:00 PM. Contact: ###-####.
|
FIR06-00242
| INSP-Final Inspection | 4/18/2006 | 4/19/2006 | 4/19/2006 4:06:13 PM | P | PASS |
|
|
Hood suppression system operated correctly under test conditions, the k class extinguisher to be relocated to the required min. distance away from hood.
|
BLD05-03484
| FIRE-Final Inspection | 4/19/2006 | 4/19/2006 | 4/19/2006 3:10:20 PM | P | NR |
|
|
Project is not completed for final inspection, to be scheduled when ready per phone conversation with contact.
|
MIS06-00078
| FIR-Final | 4/18/2006 | 4/19/2006 | 4/19/2006 3:07:11 PM | A | FAIL |
|
|
Remove manual thumbturns on the main entry/exit doors, lower fire extinguisher to no higher than 48" AFF, door hardware leading from the common shared space between tenants must meet code requirements and be operable from the inside without a key.
|
BLD06-00084
| FIRE-Final Inspection | 4/18/2006 | 4/19/2006 | 4/19/2006 2:22:45 PM | A | PASS |
|
|
Fire life safety is acceptable pending installation of lever hardware at two door locations.
|
FIR05-00699
| INSP-Final Inspection | 4/18/2006 | 4/19/2006 | 4/19/2006 1:44:48 PM | A | DEFR |
|
|
Inspection to be completed 4/20 as discussed.
|
FIR05-00576
| INSP-Final Inspection | 4/19/2006 | 4/19/2006 | 4/19/2006 1:39:17 PM | A | PASS |
|
|
The project related shell alarm permit has been completed, fire alarm finaled.
|
BLD05-02334
| FIRE-Final Inspection | 4/18/2006 | 4/19/2006 | 4/19/2006 1:35:12 PM | A | FAIL |
|
|
One exit discharge light at the courtyard is not operable, the manual exit pushbutton at the access controlled egress doors at two locations in phase two are not functional, need to add one emergency light in the corridor frist floor outside confrence rooms, provide lever hardware at the maintenance office door.
|
FIR06-00141
| INSP-Final Inspection | 4/18/2006 | 4/19/2006 | 4/19/2006 1:30:38 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR06-00211
| INSP-Final Inspection | 4/18/2006 | 4/19/2006 | 4/19/2006 1:30:00 PM | A | FAIL |
|
|
The fire sprinkler approved plans were not available on site for review or inspection, the installation appears satisfactory, however there are no plans, review notes or permit card to verify the work completed.
|
FIR05-00712
| INSP-Final Inspection | 4/18/2006 | 4/19/2006 | 4/19/2006 8:54:19 AM | A | PASS |
|
|
Required corrections have been completed, fire alarm passed final inspection.
|
BLD04-00943
| FIRE-Sprinkler Rough-in | 4/18/2006 | 4/19/2006 | 4/18/2006 4:39:50 PM | P | PART |
|
|
Overhead fire sprinkler is good for cover.
|