PLM07-00049
| Final | 4/19/2007 | 4/19/2007 | 4/19/2007 5:02:23 PM | P | FAIL |
|
|
Brian; Phone #: ###-#### Internet Inspection Request from: Stacie Backus-need to add rpba to permit-rpba needs 24" in front of test cocks & needs tested & certified.-need permit for dbcv on lawn sprinklers, needs tested & certified & uncovered for inspection & pay double permit fee.
|
PLM07-01237
| Sprinkler (Final) | 4/18/2007 | 4/19/2007 | 4/19/2007 4:19:14 PM | P | PASS |
|
|
Carol; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
|
PLM07-01236
| Final | 4/18/2007 | 4/19/2007 | 4/19/2007 4:03:02 PM | P | PASS |
|
|
The house has been removed. The Backflo is for the Common area Landscape. It is on the Northeast corner of Pierce Park Lane & Foggy Bottom St. Phone #: ###-#### Internet Inspection Request from: Pat Hurley
|
PLM07-00729
| Med/Gas Systems | 4/19/2007 | 4/19/2007 | 4/19/2007 3:27:23 PM | P | FAIL |
|
|
Pressure witness test. Phone #: ###-#### Internet Inspection Request from: Kirk Johns-need to support air line every 6'- need to support vac line every 4'- vac line needs graded 1/4" every 10'- need 150 psi on air & 15 psi on vac for 24 hr test- need stamped drawing for vac & air before final.
|
PLM07-01105
| Plumbing Rough-in | 4/19/2007 | 4/19/2007 | 4/19/2007 2:04:21 PM | P | PASS |
|
|
this was a shower & shower valve replacement.
|
PLM07-01105
| DOC - Permit Finaled | 4/19/2007 | 4/19/2007 | 4/19/2007 2:03:30 PM | P | PASS |
|
|
this was a shower & shower valve replacement
|
PLM07-01181
| Water and/or Sewer | 4/19/2007 | 4/19/2007 | 4/19/2007 1:37:34 PM | P | PART |
|
|
this was a conferance on sewer line.
|
PLM07-01058
| Water and/or Sewer | 4/18/2007 | 4/19/2007 | 4/19/2007 10:56:17 AM | A | PART |
|
|
12:00 if possible Tom; Phone #: ###-#### Internet Inspection Request from: Stacie Backus-water main up to 5' of building pass.
|
PLM07-01105
| Plumbing Rough-in | 4/18/2007 | 4/19/2007 | 4/19/2007 10:22:07 AM | A | CANC |
|
|
|
PLM06-02785
| Final | 4/18/2007 | 4/19/2007 | 4/19/2007 10:21:21 AM | A | PART |
|
|
CONTACT: RYAN Phone #: ###-#### Internet Inspection Request from: JENN STALEY-need to label nonpotible water, caulk shower valve, plug drain lines in future space, missing c/o plug in mech room, add spill proof vacuum breaker or have eye wash so cannot reach into mop sink.
|
PLM07-00982
| Final | 4/18/2007 | 4/19/2007 | 4/19/2007 9:24:15 AM | A | PART |
|
|
Call Brad please Phone #: ###-#### Internet Inspection Request from: joe paige-temp final ok, still needs to hook up ice machine & salad bar.
|