BLD09-01727
| FIRE-Final Inspection | 4/14/2010 | 4/19/2010 | 4/19/2010 4:49:08 PM | P | PART |
|
|
EM lighting and exit signs tested satisfactory, reviewed project related FIR permits and discussed items necessary for final.
|
FIR10-00055
| INSP-Final Inspection | 4/19/2010 | 4/19/2010 | 4/19/2010 4:46:53 PM | P | PASS |
|
|
Fire sprinkler permit okayed for final status.
|
FIR10-00124
| INSP-Alarm Testing | 4/19/2010 | 4/19/2010 | 4/19/2010 4:45:17 PM | P | PART |
|
|
New devices passed functional testing including the ID detector, antifreeze system tamper switches, OS&Y tampers at the double check, wet system flow switch and PIV tamper. Also tested the new area smoke detector and horn at the chemical storage room. Items needed for final include approved resubmittals showing the additional SD and horn at the chem. room, NFPA 72 record of completion report, legible labels at FACP for zone descriptors, repair the trouble conditon on the existing notification circut at the panel.
|
FIR09-00738
| INSP-Final Inspection | 4/19/2010 | 4/19/2010 | 4/19/2010 4:35:03 PM | P | PART |
|
|
|
BLD09-01739
| FIRE-Final Inspection | 4/19/2010 | 4/19/2010 | 4/19/2010 4:34:15 PM | A | PART |
|
|
See activity notes 3/25
|
BLD10-00499
| FIRE-Final Inspection | 4/19/2010 | 4/19/2010 | 4/19/2010 3:40:10 PM | P | PASS |
|
|
Life safety inspection passed.
|