FIR05-00565
| INSP-Final Inspection | 4/16/2010 | 4/19/2010 | 4/20/2010 11:01:02 AM | P | PASS |
|
|
permit finaled
|
FIR05-00210
| INSP-Final Inspection | 4/16/2010 | 4/19/2010 | 4/20/2010 11:00:38 AM | P | PASS |
|
|
permit finaled
|
FIR10-00128
| INSP-Sprinkler Rough-in | 4/19/2010 | 4/19/2010 | 4/20/2010 10:33:51 AM | P | PASS |
|
|
The sprinkler piping at the two relocated coolers on the north side of the building is ok to cover.
|
FIR10-00182
| INSP-Final Inspection | 4/19/2010 | 4/19/2010 | 4/19/2010 3:57:35 PM | P | PASS |
|
|
Permit finaled
|
FIR07-00132
| INSP-Final Inspection | 4/16/2010 | 4/19/2010 | 4/19/2010 2:15:45 PM | A | PASS |
|
|
Permit finaled
|
FIR10-00183
| INSP-Sprinkler Rough-in | 4/19/2010 | 4/19/2010 | 4/19/2010 2:05:12 PM | P | FAIL |
|
|
The work is not complete, thrust block missing, and there were no approved plans on site.
|
BLD10-00801
| FIRE-Final Inspection | 4/16/2010 | 4/19/2010 | 4/19/2010 2:04:17 PM | A | FAIL |
|
|
Remove the manual locks from the doors as indicated in red on the city approved plans, mount the fire extinguishers as discussed and marked in red on the city approved plans and repair/replace and test the exit signs and emergency lights.
|
BLD10-00087
| FIRE-Final Inspection | 4/16/2010 | 4/19/2010 | 4/19/2010 2:02:39 PM | A | FAIL |
|
|
The existing fire alarm system needs to be extended into the new common use area. All other life safety items will be ok to pass after the fire alarm issue has been addressed.
|