Inspections for the day of: Monday, April 19, 2010.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00565 INSP-Final Inspection4/16/20104/19/20104/20/2010 11:01:02 AMPPASS
permit finaled
FIR05-00210 INSP-Final Inspection4/16/20104/19/20104/20/2010 11:00:38 AMPPASS
permit finaled
FIR10-00128 INSP-Sprinkler Rough-in4/19/20104/19/20104/20/2010 10:33:51 AMPPASS
The sprinkler piping at the two relocated coolers on the north side of the building is ok to cover.
FIR10-00182 INSP-Final Inspection4/19/20104/19/20104/19/2010 3:57:35 PMPPASS
Permit finaled
FIR07-00132 INSP-Final Inspection4/16/20104/19/20104/19/2010 2:15:45 PMAPASS
Permit finaled
FIR10-00183 INSP-Sprinkler Rough-in4/19/20104/19/20104/19/2010 2:05:12 PMPFAIL
The work is not complete, thrust block missing, and there were no approved plans on site.
BLD10-00801 FIRE-Final Inspection4/16/20104/19/20104/19/2010 2:04:17 PMAFAIL
Remove the manual locks from the doors as indicated in red on the city approved plans, mount the fire extinguishers as discussed and marked in red on the city approved plans and repair/replace and test the exit signs and emergency lights.
BLD10-00087 FIRE-Final Inspection4/16/20104/19/20104/19/2010 2:02:39 PMAFAIL
The existing fire alarm system needs to be extended into the new common use area. All other life safety items will be ok to pass after the fire alarm issue has been addressed.