Inspections for the day of: Tuesday, April 19, 2011.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-01964 ELE-Aging Inspection4/19/20114/19/20114/21/2011 6:32:23 AM DONE
still under construction
ELE11-00144 ELE-Aging Inspection4/19/20114/19/20114/21/2011 6:31:05 AM DONE
still under construction
ELE10-01893 ELE-Aging Inspection4/19/20114/19/20114/21/2011 6:29:36 AM DONE
still under construction
ELE11-00186 Final4/19/20114/19/20114/19/2011 3:56:26 PMPPASS
ok
ELE10-02072 Electrical Rough-In4/19/20114/19/20114/19/2011 3:53:38 PMPPASS
call 15 min prior//Sean Phone #: ###-#### ri ok
ELE11-00763 Electrical Rough-In4/19/20114/19/20114/19/2011 3:27:14 PMPNR
Phone #: ###-#### >> Inspection requested via web by Dan Rohl electricians still working, told them to call in when ready
ELE11-00485 Electrical Rough-In4/19/20114/19/20114/19/2011 2:56:48 PMPPASS
re-inspect ceiling Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin corrections made, ok cover ceiling
ELE11-00735 Electrical Rough-In4/19/20114/19/20114/19/2011 2:22:51 PMPPASS
Underground inspection - contact is Jake Chouinard ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Campbell ok cover u/g upper area into pit
ELE11-00488 Electrical Rough-In4/18/20114/19/20114/19/2011 1:33:31 PMPPASS
CEILING INSPECTION Phone #: ###-#### >> Inspection requested via web by JENNY EMEL ok ceiling cover
ELE11-00762 Electrical Rough-In4/19/20114/19/20114/19/2011 1:12:22 PMPPASS
Eric Phone #: ###-#### ri ok
ELE11-00762 Final4/19/20114/19/20114/19/2011 1:12:12 PMPPASS
Eric Phone #: ###-#### ok final
GCE11-00039 GCE-Rough-In4/18/20114/19/20114/19/2011 11:39:00 AMAPASS
Rough-InJermey @ ###-####Call in Advance - AM Inspection Please walls and ceiling ok to cover
ELE11-00319 Final4/18/20114/19/20114/19/2011 9:49:47 AMAPASS
GARAGE CODE 1968 Phone #: ###-#### >> Inspection requested via web by Bob Glenn ok final
ELE11-00707 Rough-In Permanent Service4/18/20114/19/20114/19/2011 9:29:11 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
ELE11-00485 Electrical Rough-In4/18/20114/19/20114/19/2011 8:41:31 AMAFAIL
ceiling close Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin left correction notice, told contractor, NEC 725.25 abandoned lv cable shall be removed, 300.11(B) raceways shall not be supported by other raceways, 358.30(A) emt shall be supported within 3' of box, 348.30(A) fmc shall be supported within 12" of box, 330.30(B) mc shall be supported within 12" of box
ESC06-01133 DOC - Permit Expired4/19/20114/19/20114/19/2011 7:32:59 AMAPASS
no sign, no work done, rest of permits expired