Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00314 FIR-Aging Inspection4/19/20124/19/20124/19/2012 4:37:59 PM DEFR
FIR12-00102 INSP-Sprinkler Rough-in4/18/20124/19/20124/19/2012 4:37:01 PMPPART
Completed initial rough-in inspection at the NE portion of system 5 including the 4" grid main and 2" branchlines to column line 11. Seismic bracing at the main is not yet installed, missing retainers at all 14" beams, BL at column C is incomplete, noted additional threaded couplings at several branchlines, need to maintain seismic clearance where piping passes through non-frangible construction.
BLD12-00773 FIRE-Final Inspection4/18/20124/19/20124/19/2012 4:26:57 PMPFAIL
Correction items include items # 2, 4 and 8 on the list of general requirements attatched to the permit documents. Mount fire extinguishers no higher than 48" above finish floor, remove the manual thumbturn at one office door, missing ceiling and fire sprinkler coverage at one area in the breakroom.
BLD12-00843 FIRE-Final Inspection4/19/20124/19/20124/19/2012 4:15:06 PMPPASS
Life safety inspection completed satisfactory.
BLD12-00782 FIRE-Final Inspection4/18/20124/19/20124/19/2012 4:14:16 PMAFAIL
Provide current certification tags for the fire extinguishers at both levels, door hardware at the main entry/exit is not compliant.