| FIR-Aging Inspection | 4/19/2012 | 4/19/2012 | 4/19/2012 4:37:59 PM | | DEFR |
|
|
|
FIR12-00102
| INSP-Sprinkler Rough-in | 4/18/2012 | 4/19/2012 | 4/19/2012 4:37:01 PM | P | PART |
|
|
Completed initial rough-in inspection at the NE portion of system 5 including the 4" grid main and 2" branchlines to column line 11. Seismic bracing at the main is not yet installed, missing retainers at all 14" beams, BL at column C is incomplete, noted additional threaded couplings at several branchlines, need to maintain seismic clearance where piping passes through non-frangible construction.
|
BLD12-00773
| FIRE-Final Inspection | 4/18/2012 | 4/19/2012 | 4/19/2012 4:26:57 PM | P | FAIL |
|
|
Correction items include items # 2, 4 and 8 on the list of general requirements attatched to the permit documents. Mount fire extinguishers no higher than 48" above finish floor, remove the manual thumbturn at one office door, missing ceiling and fire sprinkler coverage at one area in the breakroom.
|
BLD12-00843
| FIRE-Final Inspection | 4/19/2012 | 4/19/2012 | 4/19/2012 4:15:06 PM | P | PASS |
|
|
Life safety inspection completed satisfactory.
|
BLD12-00782
| FIRE-Final Inspection | 4/18/2012 | 4/19/2012 | 4/19/2012 4:14:16 PM | A | FAIL |
|
|
Provide current certification tags for the fire extinguishers at both levels, door hardware at the main entry/exit is not compliant.
|