Inspections for the day of: Thursday, April 19, 2012.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00228 FIR-Aging Inspection4/19/20124/19/20124/20/2012 8:29:52 AM NR
Per Mark there is a trouble on the facp that they are waiting for Simplex to fix prior to calling for a final inspection.
FIR11-00393 FIR-Aging Inspection4/19/20124/19/20124/20/2012 8:24:34 AM NR
Per Tim with Crane Alarm the hvac units are being repaired and the permit should be called in for inspection before too long.
FIR12-00041 INSP-Sprinkler Rough-in4/18/20124/19/20124/19/2012 3:47:56 PMAPASS
The underground supply line flush passed inspection.
BLD11-02170 FIRE-Conference4/19/20124/19/20124/19/2012 3:13:51 PMPDONE
Fire sprinkler plans need to be resubmitted showing all changes in routing and fitting counts prior to covering by sheet rock. I spoke to Bruce the fitter, Tony Young and with Jerry with Petra about the issues but agreed that I would allow the installation of insulation, for sound proofing, above the piping. This insulation, it was agreed would be installed above the sprinkler piping and would not obstruct my view of the sprinkler piping for the future cover inspection.
FIR12-00133 INSP-Sprinkler Rough-in4/18/20124/19/20124/19/2012 3:08:20 PMAFAIL
The piping installation does not match the approved plans. The riser location has been changed. Pipe routing for the main and branchlines has changed. Pipe routing to and in the basement remote area has changed. Pendant head locations have changed. Pendants are supplied from different sources. Alot of additional fittings have been added including four additional elbows in the basement remote area. This does not include the additional fittigns in the supply piping to the remote area. Pendants have been relocated to soffits instead of being installed in the high ceiling areas. Also the wall layout does not match in all locations to the city approved plans. There are areas where hvac duct work is obstructing the pendant heads. Todays inspection was only for the basement area since the main level piping has not been completed yet. Plans need to be resubmitted showing all changes in routing and fitting counts prior to covering by sheet rock. I spoke to Bruce the fitter, Tony Young and with Jerry with Petra about the issues but agreed that I would allow the installation of insulation, for sound proofing, above the piping. This insulation, it was agreed would be installed above the sprinkler piping and would not obstruct my view of the sprinkler piping for the future cover inspection.
BLD12-00753 FIRE-Final Inspection4/18/20124/19/20124/19/2012 2:09:10 PMAFAIL
Repair the exit signs. Provide annual inspection for the fire extinguishers. Remove the thumbturn dead bolt at the main exit (keyed is ok). Remove the thumbturn dead bolts on the other two exit doors.
BLD12-00252 FIRE-Final Inspection4/18/20124/19/20124/19/2012 11:18:14 AMAPASS
life safety passed