FIR09-00228
| FIR-Aging Inspection | 4/19/2012 | 4/19/2012 | 4/20/2012 8:29:52 AM | | NR |
|
|
Per Mark there is a trouble on the facp that they are waiting for Simplex to fix prior to calling for a final inspection.
|
FIR11-00393
| FIR-Aging Inspection | 4/19/2012 | 4/19/2012 | 4/20/2012 8:24:34 AM | | NR |
|
|
Per Tim with Crane Alarm the hvac units are being repaired and the permit should be called in for inspection before too long.
|
FIR12-00041
| INSP-Sprinkler Rough-in | 4/18/2012 | 4/19/2012 | 4/19/2012 3:47:56 PM | A | PASS |
|
|
The underground supply line flush passed inspection.
|
BLD11-02170
| FIRE-Conference | 4/19/2012 | 4/19/2012 | 4/19/2012 3:13:51 PM | P | DONE |
|
|
Fire sprinkler plans need to be resubmitted showing all changes in routing and fitting counts prior to covering by sheet rock. I spoke to Bruce the fitter, Tony Young and with Jerry with Petra about the issues but agreed that I would allow the installation of insulation, for sound proofing, above the piping. This insulation, it was agreed would be installed above the sprinkler piping and would not obstruct my view of the sprinkler piping for the future cover inspection.
|
FIR12-00133
| INSP-Sprinkler Rough-in | 4/18/2012 | 4/19/2012 | 4/19/2012 3:08:20 PM | A | FAIL |
|
|
The piping installation does not match the approved plans. The riser location has been changed. Pipe routing for the main and branchlines has changed. Pipe routing to and in the basement remote area has changed. Pendant head locations have changed. Pendants are supplied from different sources. Alot of additional fittings have been added including four additional elbows in the basement remote area. This does not include the additional fittigns in the supply piping to the remote area. Pendants have been relocated to soffits instead of being installed in the high ceiling areas. Also the wall layout does not match in all locations to the city approved plans. There are areas where hvac duct work is obstructing the pendant heads. Todays inspection was only for the basement area since the main level piping has not been completed yet. Plans need to be resubmitted showing all changes in routing and fitting counts prior to covering by sheet rock. I spoke to Bruce the fitter, Tony Young and with Jerry with Petra about the issues but agreed that I would allow the installation of insulation, for sound proofing, above the piping. This insulation, it was agreed would be installed above the sprinkler piping and would not obstruct my view of the sprinkler piping for the future cover inspection.
|
BLD12-00753
| FIRE-Final Inspection | 4/18/2012 | 4/19/2012 | 4/19/2012 2:09:10 PM | A | FAIL |
|
|
Repair the exit signs. Provide annual inspection for the fire extinguishers. Remove the thumbturn dead bolt at the main exit (keyed is ok). Remove the thumbturn dead bolts on the other two exit doors.
|
BLD12-00252
| FIRE-Final Inspection | 4/18/2012 | 4/19/2012 | 4/19/2012 11:18:14 AM | A | PASS |
|
|
life safety passed
|