Inspections for the day of: Friday, April 19, 2013.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-00629 FIRE-Final Inspection4/19/20134/19/20134/19/2013 4:59:29 PMPPASS
life safety passed
FIR13-00030 INSP-Sprinkler Rough-in4/19/20134/19/20134/19/2013 4:57:54 PMPPASS
Sprinkler rough-in passed. Baffles are needed between many of the sprinkler heads below the mezzanine since a min. 8'-0" is needed between the heads. Jeff and I discussed options.
BLD12-01698 FIRE-Conference4/19/20134/19/20134/19/2013 4:55:49 PMPDONE
darren and I discussed fire extinguisher placement, addressing, facp room signage and emergency lighting
FIR13-00071 INSP-Sprinkler Rough-in/Hydro4/19/20134/19/20134/19/2013 3:32:15 PMAPASS
Overhead hydro passed. Rough-in inspection passed for the most part. Need to verify tie-ins to the existing system and verify that flexible cplgs get installed at the wall penatrations.
BLD13-00708 FIRE-Final Inspection4/18/20134/19/20134/19/2013 3:12:03 PMPPASS
life safety passed
FIR13-00161 INSP-Final Inspection4/18/20134/19/20134/19/2013 3:10:25 PMPPASS
Permit finaled
FIR13-00169 INSP-Final Inspection4/19/20134/19/20134/19/2013 3:09:26 PMPPASS
permit finaled
FIR13-00129 INSP-Sprinkler Rough-in4/19/20134/19/20134/19/2013 2:02:08 PMPFAIL
Suppression system failed to operate the "puff" test. Gas and power did shut off however.
BLD13-00650 FIRE-Final Inspection4/19/20134/19/20134/19/2013 1:15:52 PMPPASS
Life safety passed. I found a fire extinguisher on each level near the restrooms.
BLD13-00153 FIRE-Final Inspection4/18/20134/19/20134/19/2013 12:38:32 PMAPASS
life safety passed
FIR13-00103 INSP-Sprinkler Rough-in4/18/20134/19/20134/19/2013 11:35:21 AMACANC
don Phone #: ###-####
FIR13-00068 INSP-Sprinkler Rough-in4/18/20134/19/20134/19/2013 10:49:12 AMAPASS
See the city approved plans for locations marked "ok" in red where sprinkler piping can be covered
BLD12-02195 FIRE-Final Inspection4/16/20134/19/20134/19/2013 10:01:44 AMAFAIL
Provide occupant load sign for "75" and mount at the main exit, provide building address of min. 4" of a contrasting color, relocate the ABC fire extinguisher to 75' of all points of the building, repair the emergency lighting in the kitchen area, provide correct remote annunciator for the duct smoke detectors per IMC 606.4.1 ex #2 (did not have audible and visible alarm), hood suppression system did not function.
BLD13-00861 FIRE-Final Inspection4/18/20134/19/20134/19/2013 9:08:58 AMAFAIL
Repair the exit sign at the rear exit, provide exit sign at the front exit, provide emergency lighting in the Dining area, provide sticker at the main exit, provide re-certification/annual inspection for the hood suppression system, provide one 2a,10bc fire extinguisher and a K class for the kitchen, provide occupant load sign for "67" at the main exit in the Dining room.
BLD13-00902 FIRE-Final Inspection4/18/20134/19/20134/19/2013 9:03:47 AMAPASS
Life safety passed