Inspections for the day of: Tuesday, April 19, 2016.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00253 INSP-Conference4/19/20164/19/20164/19/2016 2:02:07 PMPDONE
Don and I discussed the pendant sprinkler spacing in the dining room. I noted insulation at the roof deck blocking upright heads and possibly overspaced upright against draftstops that are not Dons scope of work but will need addressed prior to a cover inspection being done.
BLD16-00509 FIRE-Final Inspection4/19/20164/19/20164/19/2016 1:49:43 PMPPASS
life safety passed. No exit signs marked on plans but two existing are installed
FIR15-00907 INSP-Sprinkler Rough-in/Hydro4/19/20164/19/20164/19/2016 1:29:40 PMPPASS
Overhead hydro test (200psi) passed.
BLD16-01243 FIRE-Final Inspection4/19/20164/19/20164/19/2016 1:28:43 PMPFAIL
Resubmit plans showing the additional floor area that is being occupied, remove the thumbturn dead bolt (keyed ok) and provide sticker at the exit as discussed.
BLD15-04346 FIRE-Conference4/19/20164/19/20164/19/2016 11:16:38 AMPDONE
Met sprinkler contractor and project superintendant and discussed job progress and floor slope in the fire pump room.
FIR16-00143 INSP-Sprinkler Rough-in4/19/20164/19/20164/19/2016 9:59:08 AMPPASS
See the city approved plans for location where piping can be covered with todays date.
FIR16-00153 INSP-Final Inspection4/19/20164/19/20164/19/2016 9:23:34 AMPPASS
Permit finaled
FIR07-00757 FIR-Aging Inspection4/19/20164/19/20164/19/2016 8:05:55 AM NH
Contractor is out of business
BLD16-00619 FIRE-Final Inspection4/18/20164/19/20164/19/2016 8:04:49 AMAPASS
Life safety passed. Door hardware is passage but has not been installed since doors have not arrived on site.
FIR16-00259 INSP-Final Inspection4/18/20164/19/20164/19/2016 8:03:26 AMAPASS
Permit finaled