Inspections for the day of: Wednesday, April 2, 2003.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00124 INSP-Sprinkler Rough-in/Hydro4/1/20034/2/20034/2/2003 12:00:00 AMAPASS
###-#### jim Sprinklers are ok to cover 4/2/2003 1:31:08 PM
FIR02-00359 INSP-Conference4/1/20034/2/20034/2/2003 12:00:00 AMADONE
mark; Phone #: ###-#### Discussed the placement of the remote annunciator and placement of duct smoke detectors. I gave Jim permission to cover the sprinkler piping in the old print room on the east side 1st floor 4/2/2003 9:28:11 AM
BLD02-00242 FIRE-Final Inspection4/1/20034/2/20034/2/2003 12:00:00 AMAFAIL
jim; Phone #: ###-#### No approved plans on site 4/2/2003 3:01:26 PM
MIS02-00010 FIR-Final4/2/20034/2/20034/2/2003 12:00:00 AMAPASS
fire alarm and fire life safety finaled
FIR03-00036 INSP-Alarm Testing4/1/20034/2/20034/2/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 4/1/2003 at 7:37:08 AM. Contact: ###-####.
FIR02-00032 INSP-Final Inspection4/1/20034/2/20034/2/2003 12:00:00 AMPFAIL
Call first Phil - ###-#### Most of the a/v's are overspaced and will need brighter ones or additional a/v's. We tested all of the duct detectors, one fire smoke damper, manual pulls and the single smoke detector. Still need to verify standby battery supply and all a/v's. 4/2/2003 3:49:00 PM