Inspections for the day of: Friday, April 2, 2004.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-00921 Temporary Service4/1/20044/2/20044/2/2004 12:00:00 AMAPASS
###-#### allan t/s u/g new ok 4/2/2004 10:38:10 AM
ELE04-00922 Temporary Service4/1/20044/2/20044/2/2004 12:00:00 AMAPASS
###-#### allan t/s u/g new ok 4/2/2004 10:39:53 AM
ELE04-00923 Final4/1/20044/2/20044/2/2004 12:00:00 AMAFAIL
###-#### called could not locate electrodes or see where piping was grounded or bonded contractor back filled it and covered it up whole job still needs inspection 4/2/2004 12:00:44 PM
ELE04-00785 Electrical Rough-In4/1/20044/2/20044/2/2004 12:00:00 AMAPART
Store front Rough In inspection needed. Call Richard Hill if any questions; Phone #: ###-#### Internet Inspection Request from: David Lamarque partial ok correction posted 110.26 shall provide access to door opener equipment 4/2/2004 9:07:53 AM
ELE04-00647 Final4/1/20044/2/20044/2/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 4/1/2004 at 8:57:11 PM. Contact: ###-####. ok card signed 4/2/2004 8:07:12 AM
ELE03-03652 Final3/30/20044/2/20044/2/2004 12:00:00 AMAFAIL
Richard; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes no final r/i cor. posted met owner 300.4, 300. 14 , 250.148, grd all switches 4/2/2004 9:53:36 AM
ELE04-00910 Electrical Rough-In4/1/20044/2/20044/2/2004 12:00:00 AMPPASS
warren--late pm if possible; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie walls ok 2 location suite#102 4/2/2004 2:29:35 PM
ELE04-00899 Permanent Service4/2/20044/2/20044/2/2004 12:00:00 AMPPASS
harvey ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
p/s o/h rec. ok only see added r/i 4/2/2004 1:32:06 PM
ELE04-00926 Final4/2/20044/2/20044/2/2004 12:00:00 AMPCANC
daniel; Phone #: ###-#### Internet Inspection Request from: Barbara Moore see added p/s 4/2/2004 12:26:50 PM
ELE04-00926 Permanent Service4/2/20044/2/20044/2/2004 12:00:00 AMPPASS
p/s u/g rec. ok
ELE04-00899 Electrical Rough-In4/2/20044/2/20044/2/2004 12:00:00 AMPPART
still needs bond bushings around RE washers, nothing shall exit top of sqD panel, address feed to sub panel is conduit continious and is there a fitting buried if ? call JF
ELE04-00833 Electrical Rough-In4/2/20044/2/20044/2/2004 12:00:00 AMPPART
basement apartment ok