ELE04-00921
| Temporary Service | 4/1/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | A | PASS |
|
|
###-#### allan t/s u/g new ok 4/2/2004 10:38:10 AM
|
ELE04-00922
| Temporary Service | 4/1/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | A | PASS |
|
|
###-#### allan t/s u/g new ok 4/2/2004 10:39:53 AM
|
ELE04-00923
| Final | 4/1/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | A | FAIL |
|
|
###-#### called could not locate electrodes or see where piping was grounded or bonded contractor back filled it and covered it up whole job still needs inspection 4/2/2004 12:00:44 PM
|
ELE04-00785
| Electrical Rough-In | 4/1/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | A | PART |
|
|
Store front Rough In inspection needed. Call Richard Hill if any questions; Phone #: ###-#### Internet Inspection Request from: David Lamarque partial ok correction posted 110.26 shall provide access to door opener equipment 4/2/2004 9:07:53 AM
|
ELE04-00647
| Final | 4/1/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 4/1/2004 at 8:57:11 PM. Contact: ###-####. ok card signed 4/2/2004 8:07:12 AM
|
ELE03-03652
| Final | 3/30/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | A | FAIL |
|
|
Richard; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes no final r/i cor. posted met owner 300.4, 300. 14 , 250.148, grd all switches 4/2/2004 9:53:36 AM
|
ELE04-00910
| Electrical Rough-In | 4/1/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | P | PASS |
|
|
warren--late pm if possible; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie walls ok 2 location suite#102 4/2/2004 2:29:35 PM
|
ELE04-00899
| Permanent Service | 4/2/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | P | PASS |
|
|
harvey ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
p/s o/h rec. ok only see added r/i 4/2/2004 1:32:06 PM
|
ELE04-00926
| Final | 4/2/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | P | CANC |
|
|
daniel; Phone #: ###-#### Internet Inspection Request from: Barbara Moore see added p/s 4/2/2004 12:26:50 PM
|
ELE04-00926
| Permanent Service | 4/2/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | P | PASS |
|
|
p/s u/g rec. ok
|
ELE04-00899
| Electrical Rough-In | 4/2/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | P | PART |
|
|
still needs bond bushings around RE washers, nothing shall exit top of sqD panel, address feed to sub panel is conduit continious and is there a fitting buried if ? call JF
|
ELE04-00833
| Electrical Rough-In | 4/2/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | P | PART |
|
|
basement apartment ok
|