BLD03-02762
| FIRE-Final Inspection | 3/31/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | A | PASS |
|
|
fire life safety finaled 4/2/2004 8:34:08 AM
|
FIR04-00151
| INSP-Conference | 4/1/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | A | DONE |
|
|
contractor wanted to discuss location of smoke detector over the facp and strobe locations 4/2/2004 1:00:34 PM
|
MIS04-00102
| FIR-Final | 4/1/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | A | PASS |
|
|
fire life safety finaled 4/2/2004 10:53:23 AM
|
BLD04-00134
| FIRE-Final Inspection | 4/1/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | A | FAIL |
|
|
new exit sign does not have battery backup 4/2/2004 9:14:55 AM
|
FIR04-00199
| INSP-Final Inspection | 4/1/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | A | PASS |
|
|
security doors interconnect finaled 4/2/2004 9:23:05 AM
|
FIR04-00060
| INSP-Final Inspection | 4/2/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | A | PASS |
|
|
fire sprinkler finaled
|
BLD04-00041
| FIRE-Final Inspection | 4/2/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | A | PASS |
|
|
fire life safety finaled
|
MIS04-00100
| FIR-Final | 4/2/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | P | FAIL |
|
|
Provide fire extinguisher. Remove dead bolt and provide approved door hardware on the rear door. Provide "Door to remain unlocked during business hours" on one of the front doors that is to be the main exit. Provide approved door hardware on the other front door. 4/2/2004 12:25:00 PM
|
FIR03-00648
| INSP-Final Inspection | 4/2/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | P | FAIL |
|
|
Started dtest but found multiple problems such as horn not working, smoke detector too far from deck, no breaker lock, no zone descriptions and per the general contractor the electrician still needed to program some items into the panel. The test needs to be started over 4/2/2004 3:07:09 PM
|
BLD04-00117
| FIRE-Final Inspection | 4/2/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | P | FAIL |
|
|
Relocate sprinkler pendant in the north east corner south 2'. Provide canopies and install ceiling tile. Relocate exit sign as discussed 4/2/2004 12:26:25 PM
|
FIR03-00612
| INSP-Conference | 4/2/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | P | DONE |
|
|
I spoke with the fire alarm contractor about horn/strobe placement in laundry room 4/5/2004 10:57:15 AM
|
BLD04-00134
| FIRE-Final Inspection | 4/2/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | P | PASS |
|
|
fire life safety finaled 4/2/2004 12:40:43 PM
|
BLD04-00259
| BLD-Conference | 4/2/2004 | 4/2/2004 | 4/2/2004 12:00:00 AM | P | DONE |
|
|
I left a correction notice for Jim with Steed Construction for approved door hardware to be provided on the west stairwell doors. Provide approved door hardware on the west side double doors in the first floor elevator lobby. Provide approved door hardware on exit doors from suite 200 (three total). Repair or replace exit signs on second floor egress corridors and first floor lobby (six total). Provide emergency lighting in second floor egress corridors and first floor lobby. 4/5/2004 11:04:41 AM
|