Inspections for the day of: Monday, April 2, 2007.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01052 Temporary Service4/2/20074/2/20074/2/2007 4:02:04 PMPPASS
CONTACT JACK 9410621
t/s u/g new ok
ELE07-01076 Electrical Rough-In4/1/20074/2/20074/2/2007 3:57:10 PMPFAIL
Phone #: ###-#### corr. called 300.14 6" free length all locations, 110/14(B) loose crimp sleeves equip. grds, 300.4 (A)(1&(D) nail plates and 11/4" cables parallel to studs, 210.11(C)(2) all recepts in laundry shall be on laundry rm 20 amp circuit, 314.43 remove screw from inside of box in front soofit
ELE07-01076 Permanent Service4/2/20074/2/20074/2/2007 3:22:18 PMPPASS
Phone #: ###-#### p/s u/g new ok
ELE07-00540 Rough-In Permanent Service4/2/20074/2/20074/2/2007 2:43:16 PMPFAIL
jade; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr. fee due called left message, all violations not made and new ones created, 300.14 6" free conductor, 300.4(D) 11/4" cables parallel to studs, 300.15 boxes required all locations outside fixtures,110.3(A) replace broken box kit., 210.52(B) remove range hood, back entry recept and anything eles not allowed on SABC, 314.43 no screws or nails allowed in plastic boxes
ELE07-00540 Permanent Service4/2/20074/2/20074/2/2007 2:36:08 PMPPASS
jade; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s o/h rec. ok
ELE07-00376 Permanent Service3/28/20074/2/20074/2/2007 1:58:19 PMPPASS
Jack, #4 GEC installed to water main, Hot h20 heater bonded around all fittings.Done! thanks Loren Phone #: ###-#### see added final
ELE07-00376 Final4/2/20074/2/20074/2/2007 1:57:45 PMPPASS
Jack, #4 GEC installed to water main, Hot h20 heater bonded around all fittings.Done! thanks Loren Phone #: ###-#### ok
ELE07-01077 Rough-In Permanent Service4/2/20074/2/20074/2/2007 1:34:17 PMPPART
9411710 walls ok no p/s meter needs ID
ELE07-00752 Rough-In Permanent Service4/2/20074/2/20074/2/2007 12:55:27 PMPPASS
On site journeyman - Gene ###-####
Thank you!! Phone #: ###-####
r/i p/s u/g new new ok all 4 units
ELE06-00461 Final4/2/20074/2/20074/2/2007 12:13:18 PMPPASS
marshall; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok
ELE06-04673 Final3/30/20074/2/20074/2/2007 11:00:07 AMAFAIL
Phone #: ###-#### corr. fee due called 410.8 &404.4 needs enclosed for closets, shower trims for wet, also install shelves and rods in closet for clearence check
ELE07-00833 Electrical Rough-In3/30/20074/2/20074/2/2007 10:35:33 AMAFAIL
Cover...Ryan; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
corr. do not cover called left message
300.4(A)(1)&(D) nail plates and 11/4", 250.32(B)(2) terminate GEC at neutral bus and install bond screw, 110.3(B) shall install main breaker per manu. instructions panel used as lighting panel, all 3 garages
ELE07-01075 Electrical Rough-In3/30/20074/2/20074/2/2007 9:44:07 AMANH
bath and utility area, thank you Phone #: ###-#### x0000 notice posted
ELE07-01073 Electrical Rough-In3/30/20074/2/20074/2/2007 9:33:45 AMAPASS
paul ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
r/i ok
ELE07-00494 Electrical Rough-In3/30/20074/2/20074/2/2007 8:55:09 AMAPASS
Phone #: ###-#### r/i ok corrections made
ELE07-00764 Final4/2/20074/2/20074/2/2007 8:40:36 AMPPASS
Phone #: ###-#### ok
ELE07-00951 Final3/31/20074/2/20074/2/2007 8:23:33 AMAPASS
Phone #: ###-#### ok no card