ELE06-02816
| Final | 4/2/2007 | 4/2/2007 | 4/2/2007 4:08:22 PM | P | PASS |
|
|
ok to final
|
ELE07-00285
| Final | 4/2/2007 | 4/2/2007 | 4/2/2007 3:56:36 PM | P | PASS |
|
|
wayne; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corrections made, ok to cover u/g, called contr to ensure backfill not big rocks, but sand, close ko's, ok to final
|
ELE07-00890
| Final | 4/1/2007 | 4/2/2007 | 4/2/2007 3:14:37 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 4/1/2007 at 12:31:05 PM. Contact: ###-####. ok to final
|
ELE07-00890
| Rough-In Permanent Service | 4/2/2007 | 4/2/2007 | 4/2/2007 3:12:51 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 4/1/2007 at 12:31:05 PM. Contact: ###-####. ric ok, p/s u/g rec ok
|
ELE07-00677
| Electrical Rough-In | 4/2/2007 | 4/2/2007 | 4/2/2007 2:42:29 PM | P | PASS |
|
|
neil; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok upper and lower
|
ELE07-01046
| Temporary Service | 4/2/2007 | 4/2/2007 | 4/2/2007 1:11:42 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 4/2/2007 at 9:29:49 AM. Contact: ###-####. called, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 250.53(G) rod shall be flush with or below ground level, 110.12(C) there shall be no broken parts or foreign material in panel, 110.13(A) equipment shall be firmly secured
|
ELE06-04177
| Final | 4/2/2007 | 4/2/2007 | 4/2/2007 12:49:01 PM | P | PASS |
|
|
CAL BISHOP - WILL MEET @ JOBSITE Phone #: ###-#### contr called to tie to bld, elect will put on labels, ok to final, signed occ card
|
ELE07-01071
| Rough-In Permanent Service | 3/30/2007 | 4/2/2007 | 4/2/2007 10:57:39 AM | A | PASS |
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called contr about 1 1/4" and addresses, ri ok, p/s u/g n ok
|
ELE07-00076
| Final | 3/30/2007 | 4/2/2007 | 4/2/2007 10:03:01 AM | A | FAIL |
|
|
Brandon; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called, left corr notice, nec 210.52(E) shall install recpt at rear of dwelling, 210.70(A)(3) shall install lighting for jetted tub access and verify access hole per mfgr's instructions, 410.8(D) flourescent fixt in closet shall be min 6'' from shelf, 406.5 recpt faceplates shall seat against mounting surface, NOTE: shall provide cover for gec on dwelling and finish nailplates in garage
|
ELE07-01065
| Temporary Service | 3/30/2007 | 4/2/2007 | 4/2/2007 9:25:15 AM | A | FAIL |
|
|
Brandon; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called, left corr notice, nec 404.8 center of upper bkr handle shall not be over 6"- 7" high, 408.4 shall provide circuit directory, 312.5 abrasion protection shall be provided for all conductors entering enclosures
|
ELE07-00996
| Permanent Service | 3/29/2007 | 4/2/2007 | 4/2/2007 9:04:17 AM | A | NH |
|
|
200amp service upgrade, new circuit to water heater.Any questions call Tate @###-#### Phone #: ###-#### called, told contr we need access, recall when can get in
|
ELE07-01069
| Temporary Service | 3/30/2007 | 4/2/2007 | 4/2/2007 8:49:26 AM | A | FAIL |
|
|
shawn ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left corr notice, left message, nec 250.24(A) system shall be grounded vis grounding electrode,BCC address shall be correct, gec abrasion protection shall not be 2 screw conn
|
ELE06-04592
| Final | 3/30/2007 | 4/2/2007 | 4/2/2007 8:29:04 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 3/30/2007 at 1:44:46 PM. Contact: ###-####. ok to final, signed card
|
ELE07-01003
| Electrical Rough-In | 4/2/2007 | 4/2/2007 | 4/2/2007 12:00:00 AM | P | CANC |
|
|
MITCH PAGE - WILL MEET @ JOBSITE Phone #: ###-####
|