Inspections for the day of: Monday, April 2, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02816 Final4/2/20074/2/20074/2/2007 4:08:22 PMPPASS
ok to final
ELE07-00285 Final4/2/20074/2/20074/2/2007 3:56:36 PMPPASS
wayne; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corrections made, ok to cover u/g, called contr to ensure backfill not big rocks, but sand, close ko's, ok to final
ELE07-00890 Final4/1/20074/2/20074/2/2007 3:14:37 PMPPASS
Scheduled by a contractor via Hello! on 4/1/2007 at 12:31:05 PM. Contact: ###-####. ok to final
ELE07-00890 Rough-In Permanent Service4/2/20074/2/20074/2/2007 3:12:51 PMPPASS
Scheduled by a contractor via Hello! on 4/1/2007 at 12:31:05 PM. Contact: ###-####. ric ok, p/s u/g rec ok
ELE07-00677 Electrical Rough-In4/2/20074/2/20074/2/2007 2:42:29 PMPPASS
neil; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok upper and lower
ELE07-01046 Temporary Service4/2/20074/2/20074/2/2007 1:11:42 PMPFAIL
Scheduled by a contractor via Hello! on 4/2/2007 at 9:29:49 AM. Contact: ###-####. called, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 250.53(G) rod shall be flush with or below ground level, 110.12(C) there shall be no broken parts or foreign material in panel, 110.13(A) equipment shall be firmly secured
ELE06-04177 Final4/2/20074/2/20074/2/2007 12:49:01 PMPPASS
CAL BISHOP - WILL MEET @ JOBSITE Phone #: ###-#### contr called to tie to bld, elect will put on labels, ok to final, signed occ card
ELE07-01071 Rough-In Permanent Service3/30/20074/2/20074/2/2007 10:57:39 AMAPASS
brandon; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called contr about 1 1/4" and addresses, ri ok, p/s u/g n ok
ELE07-00076 Final3/30/20074/2/20074/2/2007 10:03:01 AMAFAIL
Brandon; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called, left corr notice, nec 210.52(E) shall install recpt at rear of dwelling, 210.70(A)(3) shall install lighting for jetted tub access and verify access hole per mfgr's instructions, 410.8(D) flourescent fixt in closet shall be min 6'' from shelf, 406.5 recpt faceplates shall seat against mounting surface, NOTE: shall provide cover for gec on dwelling and finish nailplates in garage
ELE07-01065 Temporary Service3/30/20074/2/20074/2/2007 9:25:15 AMAFAIL
Brandon; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called, left corr notice, nec 404.8 center of upper bkr handle shall not be over 6"- 7" high, 408.4 shall provide circuit directory, 312.5 abrasion protection shall be provided for all conductors entering enclosures
ELE07-00996 Permanent Service3/29/20074/2/20074/2/2007 9:04:17 AMANH
200amp service upgrade, new circuit to water heater.Any questions call Tate @###-#### Phone #: ###-#### called, told contr we need access, recall when can get in
ELE07-01069 Temporary Service3/30/20074/2/20074/2/2007 8:49:26 AMAFAIL
shawn ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left corr notice, left message, nec 250.24(A) system shall be grounded vis grounding electrode,BCC address shall be correct, gec abrasion protection shall not be 2 screw conn
ELE06-04592 Final3/30/20074/2/20074/2/2007 8:29:04 AMAPASS
Scheduled by a contractor via Hello! on 3/30/2007 at 1:44:46 PM. Contact: ###-####. ok to final, signed card
ELE07-01003 Electrical Rough-In4/2/20074/2/20074/2/2007 12:00:00 AMPCANC
MITCH PAGE - WILL MEET @ JOBSITE Phone #: ###-####