BLD06-02787
| FIRE-Alarm Testing | 3/30/2007 | 4/2/2007 | 4/3/2007 4:44:06 PM | P | PART |
|
|
Room 106 is acceptable for occupancy, permit final pending completion of the remainder of the scope of work.
|
FIR06-00101
| INSP-Final Inspection | 4/2/2007 | 4/2/2007 | 4/3/2007 4:42:26 PM | P | PASS |
|
|
Required corrections have been verified for compliance, final fire sprinkler inspection passed, permit finaled.
|
FIR06-00523
| INSP-Alarm Testing | 4/2/2007 | 4/2/2007 | 4/2/2007 2:33:17 PM | P | FAIL |
|
|
See comments per inspection completed by M. Timmerman.
|
BLD07-00673
| FIRE-Conference | 3/30/2007 | 4/2/2007 | 4/2/2007 2:30:15 PM | A | DONE |
|
|
On site visit to determine requirements for project related fire sprinkler modifications and permit work.
|
FIR06-00897
| INSP-Sprinkler Rough-in/Hydro | 3/30/2007 | 4/2/2007 | 4/2/2007 2:25:36 PM | A | FAIL |
|
|
OH hydrostatic test of the antifreeze system failed due to visible leakage at the system piping, OH hydro test of the wet system failed due to pressure drop at the guage below 200psi.
|
FIR06-00101
| INSP-Sprinkler Rough-in/Hydro | 4/2/2007 | 4/2/2007 | 4/2/2007 12:00:00 AM | P | CANC |
|
|