Inspections for the day of: Wednesday, April 2, 2008.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00766 INSP-Final Inspection4/1/20084/2/20084/2/2008 5:13:55 PMPFAIL
Project was not complete. Ceiling finishes had not been completed yet (both painted and wood). I noted to the sprinkler contractor several sprinkler esch. that had been painted. Bell was not installed yet.
FIR08-00007 INSP-Final Inspection4/2/20084/2/20084/2/2008 3:40:36 PMPPASS
Permit finaled. The signal transmitted as a supervisory.
FIR06-00011 INSP-Final Inspection4/2/20084/2/20084/2/2008 3:39:38 PMPFAIL
This inspection was for the new sliding window on the second floor. The office side smoke detector was mounted less than 3' from a supply air register. The register will need to be moved. No items were tested.
FIR08-00174 INSP-Sprinkler Rough-in4/1/20084/2/20084/2/2008 1:06:11 PMAPASS
The nine pendants in the hardlids located at the front of the store as marked on the plans are ok to cover.
FIR08-00147 INSP-Final Inspection4/1/20084/2/20084/2/2008 11:27:34 AMAFAIL
All of the wall mounted strobes are mounted too high. The duct smoke detectors are not sampling all of the airflow. The fire alarm wiring in the attic space has not been attached to the building structure as required per NEC. No testing was performed.
FIR07-00929 INSP-Sprinkler Rough-in4/1/20084/2/20084/2/2008 8:43:43 AMAPASS
24hr Air Test started at 8:30 the left system has 45 psi and the right system has 44 psi.
FIR07-00766 INSP-Final Inspection4/1/20084/2/20084/1/2008 1:42:02 PMACANC
terry Phone #: ###-#### Inspection cancelled from web by: John Warnick