Inspections for the day of: Thursday, April 2, 2009.
Number of inspections: 10
Percentage of inspections complete: 90 %
Percentage of inspections not complete: 10 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00255 INSP-Final Inspection3/27/20093/27/2009 P 
Contact Rafe Phone#: ###-####
FIR09-00137 INSP-Final Inspection4/1/20094/2/20094/2/2009 4:16:44 PMPPASS
Items on issued correction notice verified for completion, fire sprinkler permit finaled.
FIR08-00737 INSP-Sprinkler Rough-in/Hydro4/2/20094/2/20094/2/2009 4:14:52 PMPPART
New dry system piping hydrostatic test completed, discussed schedule for 24 hr. air testing next week.
FIR07-01051 INSP-Sprinkler Rough-in4/1/20094/2/20094/2/2009 4:11:56 PMPPART
See approved plans for overhead okayed for cover at drop ceilings 1st and 2nd floors various locations, also approved dry pendent install at the kitchen coolers.
BLD09-00080 FIRE-Final Inspection4/2/20094/2/20094/2/2009 2:07:03 PMPPASS
Noted correction items finished, fire life safety finaled.
FIR08-00835 FIR-Aging Inspection4/2/20094/2/20094/2/2009 2:06:07 PM DONE
Work in progress construction underway.
FIR09-00135 INSP-Final Inspection4/2/20094/2/20094/2/2009 2:04:55 PMAPASS
Final fire sprinkler inspection passed, permit finaled.
FIR09-00163 INSP-Final Inspection4/1/20094/2/20094/2/2009 2:03:58 PMAPASS
Fire alarm testing completed acceptable after corrections made while on site, verified as-builts for field modifications, permit finaled.
FIR08-00766 INSP-Sprinkler Rough-in/Hydro4/2/20094/2/20094/2/2009 1:45:42 PMAPART
See dated plan notes for UG installation work okayed.
BLD09-00301 FIRE-Final Inspection4/2/20094/2/20094/2/2009 1:44:08 PMAPART
See plan annotations for work completed to date.