FIR07-00745
| INSP-Conference | 3/26/2009 | 3/27/2009 | | P | |
|
|
Inspection follow up.
|
BLD08-01210
| FIRE-Conference | 4/2/2009 | 4/2/2009 | 4/2/2009 3:38:16 PM | P | DONE |
|
|
Dale and I went over fire extinguisher placement and placement of the knox key box.
|
BLD08-02587
| FIRE-Final Inspection | 4/2/2009 | 4/2/2009 | 4/2/2009 3:07:58 PM | P | CANC |
|
|
Could not perform inspection due to time costraints. Per the contractor it will be rescheduled for tomorrow morning.
|
FIR09-00154
| INSP-Sprinkler Rough-in | 4/1/2009 | 4/2/2009 | 4/2/2009 2:57:09 PM | A | PASS |
|
|
The sprinkler piping is ok to cover.
|
FIR08-00550
| INSP-Final Inspection | 4/1/2009 | 4/2/2009 | 4/2/2009 1:47:00 PM | A | FAIL |
|
|
Plans need to be resubmitted for "plan modifications". This is due to extensive audio/visual modifications required such as additional devices, relocated devices and devices that need the candella adjusted brighter. Also the second floor tenant "ABC Channell 6" has a door magnet securing the exit door. The fire alarm contractor and I spoke about minimum sound requirements in the radio transmission rooms where only strobes had been installed and for all rooms. No devices were actually tested. An EOL had to be relocated in the NAC panel so that it would report a trouble
|
BLD08-02373
| FIRE-Final Inspection | 4/2/2009 | 4/2/2009 | 4/2/2009 11:56:33 AM | P | PASS |
|
|
Life safety passed
|
FIR09-00184
| INSP-Final Inspection | 4/2/2009 | 4/2/2009 | 4/2/2009 11:56:05 AM | P | PASS |
|
|
Permit finaled
|
FIR09-00184
| INSP-Alarm Testing | 4/1/2009 | 4/2/2009 | 4/2/2009 11:55:47 AM | A | PASS |
|
|
Permit finaled
|
BLD08-02373
| FIRE-Final Inspection | 4/2/2009 | 4/2/2009 | 4/2/2009 11:49:47 AM | P | PASS |
|
|
LIfe safety passed
|
BLD09-00277
| FIRE-Final Inspection | 4/1/2009 | 4/2/2009 | 4/2/2009 11:42:55 AM | A | PASS |
|
|
Life safety passed
|
FIR09-00187
| INSP-Final Inspection | 4/1/2009 | 4/2/2009 | 4/2/2009 11:42:03 AM | A | PASS |
|
|
The hood suppression systems operated correctly.
|
FIR09-00188
| INSP-Final Inspection | 4/1/2009 | 4/2/2009 | 4/2/2009 9:50:15 AM | A | PASS |
|
|
permit finaled
|
BLD08-00178
| FIRE-Final Inspection | 3/31/2009 | 4/2/2009 | 4/2/2009 8:39:37 AM | A | PASS |
|
|
life safety passed
|
FIR08-00716
| INSP-Final Inspection | 4/2/2009 | 4/2/2009 | 4/2/2009 8:38:58 AM | P | PASS |
|
|
permit finaled
|
FIR08-00716
| INSP-Alarm Testing | 3/31/2009 | 4/2/2009 | 4/2/2009 8:36:16 AM | A | PASS |
|
|
permit finaled
|
FIR09-00169
| INSP-Final Inspection | 4/1/2009 | 4/2/2009 | 4/2/2009 7:20:55 AM | A | PASS |
|
|
Permit finaled. The wrong cover plates had been installed between a horn/strobe and a strobe only. They were corrected as I waited.
|