Inspections for the day of: Monday, April 2, 2012.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-01662 ELE-Aging Inspection4/2/20124/2/20124/3/2012 10:17:40 AM DONE
waiting for contractor to request inspection
ELE11-01682 ELE-Aging Inspection4/2/20124/2/20124/3/2012 7:30:56 AM DONE
ELE12-00648 Permanent Service4/2/20124/2/20124/2/2012 3:13:35 PMPFAIL
jarred Phone #: ###-#### called 110.26(F)(2), needs guy kit for mast, no access
ELE12-00428 Electrical Rough-In4/2/20124/2/20124/2/2012 3:09:26 PMPPASS
eric please call before going out Phone #: ###-####
ELE12-00641 Electrical Rough-In4/2/20124/2/20124/2/2012 2:48:45 PMPPASS
Jared Phone #: ###-#### walls ok
ELE12-00650 Electrical Rough-In4/2/20124/2/20124/2/2012 2:48:23 PMPPASS
Dino Phone #: ###-#### r/i p/s u/g new ok
ELE11-00768 Final4/2/20124/2/20124/2/2012 1:15:06 PMPPASS
marion Phone #: ###-#### ok
ELE12-00628 Rough-In Permanent Service3/30/20124/2/20124/2/2012 12:00:47 PMAFAIL
Please contact Cody ###-#### with any questions. Phone #: ###-#### >> Inspection requested via web by Tracy Robertson called see added p/s, hot and cold water lines too close to recess cans
plumbing will move lines
ELE12-00628 Permanent Service4/2/20124/2/20124/2/2012 11:58:45 AMAPASS
Please contact Cody ###-#### with any questions. Phone #: ###-#### >> Inspection requested via web by Tracy Robertson p/s u/g new ok
ELE12-00650 Rough-In Permanent Service4/2/20124/2/20124/2/2012 11:58:05 AMAPASS
###-#### called protect cables within 6ft of attic access, remove range hood from microwave circuit 110.3(B) manufactures instructions r/i p/s u/g new ok
ELE12-00659 Temporary Service3/31/20124/2/20124/2/2012 11:55:27 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson
250.53(G)
ELE12-00658 Temporary Service3/31/20124/2/20124/2/2012 11:54:59 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson
called corr. 250.53(G) grd rod less than 45 degrees of vertical
ELE12-00304 Final3/30/20124/2/20124/2/2012 11:49:27 AMAPASS
Please contact Cody ###-#### with any questions Phone #: ###-#### >> Inspection requested via web by Tracy Robertson ok