Inspections for the day of: Monday, April 2, 2012.
Number of inspections: 11
Percentage of inspections complete: 91 %
Percentage of inspections not complete: 9 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-00870 FIRE-Conference3/14/20123/28/2012 A 
Please check on this and let Barb @ permit desk know status-want to try to close out permit-Thanks
BLD10-00997 FIRE-Conference4/2/20124/2/20124/2/2012 3:41:27 PMPDONE
I spoke to mike about getting a life safety final on this project.
BLD12-00221 FIRE-Conference4/2/20124/2/20124/2/2012 3:33:17 PMPDONE
I spoke to Mike about getting a life safety inspection completed for BLD10-00997 which is related to this project.
FIR12-00127 INSP-Sprinkler Rough-in4/2/20124/2/20124/2/2012 3:32:18 PMPCANC
duplicate inspection
BLD11-03036 FIRE-Conference4/2/20124/2/20124/2/2012 3:31:48 PMPDONE
I found a roof penatration (3'x3') that has been blocked off. This penatration is not shown on the city approved plans. I requested a responce from the engineer, who designed changes to the smoke evac system for this project, too provide verification that the smoke evac. system is not effected by blocking this penatration.
FIR12-00127 INSP-Final Inspection4/2/20124/2/20124/2/2012 3:21:33 PMPFAIL
Three upright sprinkler heads are painted/covered over the sales floor, two esch. are missing at the main exit, sprinkler protection needs to be provided in the empty spaced created by the new tenant demizing wall as discussed.
FIR12-00134 INSP-Final Inspection4/2/20124/2/20124/2/2012 3:20:59 PMPFAIL
Three upright sprinkler heads are painted/covered over the sales floor, two esch. are missing at the main exit, sprinkler protection needs to be provided in the empty spaced created by the new tenant demizing wall as discussed.
BLD12-00668 FIRE-Final Inspection3/30/20124/2/20124/2/2012 3:18:36 PMPFAIL
Provide information on the storage and use of flammable and combustible liquids to the plan reviewer. See IFC 2211.2, Provide sources of ignition that are located less than 18". See IFC 2211.3, Relocate the fire extinguisher to within 30' of all points in space.
BLD08-00986 FIRE-Final Inspection4/2/20124/2/20124/2/2012 3:00:12 PMPPASS
Life safety passed. The builder has installed "tabs" on the lower leaf to operate the upper leaf as a single unit.
BLD12-00172 FIRE-Final Inspection3/30/20124/2/20124/2/2012 10:38:47 AMAPASS
Life safety passed.
BLD12-00293 FIRE-Final Inspection3/30/20124/2/20124/2/2012 9:21:43 AMAPASS
Life safety passed