Inspections for the day of: Wednesday, April 2, 2014.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00789 Conference4/1/20144/2/20144/2/2014 3:57:56 PMPDONE
Please call ahead for access - Chris Phone #: ###-#### Discussed codes for master bath remodel. Dedicated 20 amp circuit needed for bath receptical. Owner to pull deicated wire from old fused panel to outlet and will dedicate when service change is done.
ELE14-00686 Rough-In Permanent Service4/1/20144/2/20144/2/2014 2:49:38 PMAPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn p/s u/g n ok Rough in ok cover
ELE14-00375 Electrical Rough-In4/1/20144/2/20144/2/2014 2:07:15 PMPCANC
early please - Rick - please call 1/2 hr prior for access Phone #: ###-####
ELE14-00375 Permanent Service4/2/20144/2/20144/2/2014 2:06:53 PMPPASS
early please - Rick - please call 1/2 hr prior for access Phone #: ###-#### p/s o/h rec ok
ELE14-00635 Final4/1/20144/2/20144/2/2014 1:40:41 PMAPASS
If you have any questions, please call Clay ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clay Morgan Final ok
ELE14-00298 Final4/2/20144/2/20144/2/2014 1:19:47 PMAFAIL
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson 210.8- All 120 volt receptical outlets shall have GFCI protection, cabinet spec in utility room shows sink, outlet on counter not protected
ELE14-00782 Electrical Rough-In4/1/20144/2/20144/2/2014 9:47:05 AMAPART
Foe Access please call Don 1/2 hr prior to inspection. ###-#### Phone #: ###-#### >> Inspection requested via web by Terry Scott BCC 4-05-32 code violation not to be retained, feeders to sub panel shall be protected from physical damage. 300.4 NEC. Kitchen rough in ok cover
ELE14-00794 Electrical Rough-In4/2/20144/2/20144/2/2014 9:19:57 AMAPASS
Would like a consultation since I have made major improvements to the electrical at this residence. I still have questions whether the city will require me to do more considering the extent I''ve rewired much of it. I''d also like approval for the drywall guy to cover & patch sheetrock throughout the house. I will be available on site only until 12p today. Phone #: ###-#### >> Inspection requested via web by nathan palmer All receptical wiring changed to 3 wire through out. rough in ok cover
ELE12-02735 Electrical Rough-In4/1/20144/2/20144/2/2014 8:51:36 AMAPASS
We are requesting a partial wall rough-in inspection for tomorrow 4/2/14 in the AM. Our onsite contact is Bud @ ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Phase 3 all exam rooms wall rough in ok cover