BLD15-00120
| FIRE-Final Inspection | 4/2/2015 | 4/2/2015 | 4/3/2015 6:55:02 AM | P | CANC |
|
|
|
FIR14-00912
| INSP-Sprinkler Rough-in | 4/1/2015 | 4/2/2015 | 4/2/2015 4:28:23 PM | P | PART |
|
|
Initial walkthrough completed- items noted include; overspaced coverage at one location in the basement, DSW not yet installed at the basement, PIV and FDC must remain accessible, heat trace and insulation fill at the combustible concealed space grade level not yet complete, provide an intermediate temp head below the second floor skylight.
________________
Add by TRF 4/06/2015
The sprinkler in the opening on the porch is incorrect it is a QR pendent. The sprinkler is supposed to be a horizontal sidewall spraying DOWN to create a water curtian affect.
|
BLD15-00639
| FIRE-Final Inspection | 4/2/2015 | 4/2/2015 | 4/2/2015 4:23:05 PM | P | FAIL |
|
|
Modifications to the existing fire sprinkler system will be necessary due to remodel work. Refer to permit documents and approved plan notes sheet A2.1.
|
BLD14-01937
| FIRE-Conference | 4/2/2015 | 4/2/2015 | 4/2/2015 4:18:25 PM | P | DONE |
|
|
Regarding project related fire sprinkler work.
|
BLD15-00354
| FIRE-Final Inspection | 4/2/2015 | 4/2/2015 | 4/2/2015 4:16:54 PM | P | NR |
|
|
Project is not in condition for inspection at this time- Construction underway.
|
FIR14-00673
| INSP-Final Inspection | 4/1/2015 | 4/2/2015 | 4/2/2015 12:37:46 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR14-00600
| INSP-Final Inspection | 4/1/2015 | 4/2/2015 | 4/2/2015 12:36:50 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR14-00814
| INSP-Final Inspection | 4/2/2015 | 4/2/2015 | 4/2/2015 9:33:50 AM | P | PASS |
|
|
UG fire supply line permit final approved.
|
FIR14-00867
| INSP-Final Inspection | 4/2/2015 | 4/2/2015 | 4/2/2015 9:31:11 AM | A | PASS |
|
|
Final walkthrough and acceptance testing completed acceptable. Fire sprinkler permit finaled.
|
FIR14-00810
| INSP-Final Inspection | 4/1/2015 | 4/2/2015 | 4/2/2015 9:29:02 AM | A | PASS |
|
|
Fire alarm testing completed satisfactory. Permit finaled.
|