Inspections for the day of: Monday, April 2, 2018.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01160 Final3/30/20184/2/20184/2/2018 3:02:19 PMPPART
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
TCO for unisex bathroom and corridor only. TCO ok
ELE18-00569 Final4/2/20184/2/20184/2/2018 3:02:07 PMPFAIL
2nd notice- Corrections from 2-13-18.
300.15- All wiring shall terminate in a box. Front sign wiring on roof.
330.30(B)- MC shall be secured with in 12" of a box. Under cabinet receptacles.
356.30- Non-metallic seal tight on east condensing unit shall be secured with in 12" of terminations.
404.8- Circuit directories shall be updated. Ensure all wiring not being used disconnected.
314.17(A)- All unused openings shall be closed by approved means. West condencing units removed. Open KOs.
406.6- Receptacles shall have proper covers installed. Back room receptacle recessed in wall with caulking as cover.
7 Working days to complete, will revisit
4-12-18. If not action has been taken a activity hold will be accessed to parcel and no work or inspections will be allowed once accessed.
Manager scanned and forwarded to supervisor while 2nd correction delivered.
ELE18-01160 Electrical Rough-In4/2/20184/2/20184/2/2018 2:14:45 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Portion of grid from salon and coffee Tenant improvements to restroom rough in ok cover
ELE18-01243 Electrical Rough-In4/2/20184/2/20184/2/2018 1:27:43 PMPNH
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg
No answer at door, Dogs barking. Called contact and asked to recall when someone available to meet on site due to house occupied.
ELE18-00477 Final4/2/20184/2/20184/2/2018 10:33:52 AMAPASS
FINAL ELECTRICAL FOR PYLON AND WALL SIGN ON MAPLE GROVE
IF QUESTIONS CALL AARON ###-#### Inspection requested via web by Dana Vance Final ok
ELE18-00477 Electrical Rough-In4/2/20184/2/20184/2/2018 10:33:35 AMPPASS
FINAL ELECTRICAL FOR PYLON AND WALL SIGN ON MAPLE GROVE
IF QUESTIONS CALL AARON ###-#### Inspection requested via web by Dana Vance
Listing and disconnecting means confirmed rough in ok.
ELE18-00408 Electrical Rough-In3/30/20184/2/20184/2/2018 9:47:46 AMAPASS
We need an underground inspection. Travis will be the contact.
Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker
Interior still shut down due to mold issue. Service entrance conduits on rear of building rough in ok cover.
ELE18-00566 Final3/30/20184/2/20184/2/2018 9:11:05 AMAPASS
Chad VanOrden is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Furniture to be free standing with no electrical. No card posted. Final ok
ELE17-02502 Final4/2/20184/2/20184/2/2018 8:32:24 AMAPASS
Phone #: ###-#### Inspection requested via web by Dana Vance
Final ok
ELE17-02502 Electrical Rough-In4/2/20184/2/20184/2/2018 8:32:10 AMPPASS
Phone #: ###-#### Inspection requested via web by Dana Vance
Listing confirmed rough in ok