Inspections for the day of: Thursday, April 2, 2020.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00833 Electrical Rough-In4/2/20204/2/20204/2/2020 2:09:20 PMPPASS
Trench inspection from garage to house. Phone #: ###-#### Inspection requested via web by Barbara Szurgot
Underground noted rough in ok cover.
ELE20-01151 Electrical Rough-In4/2/20204/2/20204/2/2020 1:28:02 PMPPASS
Underground and bonding for swimming pool. Access granted through right side of residence. Homeowner working inside detached shed if any questions Phone #: ###-#### Inspection requested via web by Lars Johnson
Bonding from equipment to shell with 4 stubs for E.Q. Underground and bonding rough in ok cover.
ELE20-01160 Rough-In Permanent Service4/1/20204/2/20204/2/2020 10:37:20 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok
ELE20-00277 Permanent Service4/1/20204/2/20204/2/2020 9:48:24 AMAFAIL
Matt. Phone #: ###-#### Inspection requested via web by Sean DeLacy
250.24(A)(1)- Grounding electrode conductors shall terminate a the same terminal or bus as the grounded conductor.
250.50- All grounding electrode discribe in 250.52 1 thru 7 shall be used to create a grounding electrode system.
250.64(C)- Grounding electrode conductors shall be continuous from service termination to grounding electrodes. Grounding electrode conductors to metal underground water pipes shall terminate with in 5' of where pipe enters structure.
250.66- Grounding electrodes to underground metel water pipes shall be #2 copper or 1/0 aluminum minimum.
ELE20-00372 Electrical Rough-In4/1/20204/2/20204/2/2020 8:53:26 AMACANC
Home owners will be there. Name is mike. Wired the basement. There is one outlets in the family Room for the TV is going to go on a brick wall that he wasn''t sure and how hes gonna finish it. So the Box is not secure but can be at any time just letting you know any questions or concerns please let me know thank you. Phone #: ###-#### Inspection requested via web by David Kubik
As per Jason Blais Building official and Mark Lavin PDS Director inspections for occupied homes have been suspended until April 17, 2020. Called and informed electrical contractor.