FIR19-00804
| INSP-Sprinkler Rough-in | 4/2/2020 | 4/2/2020 | 4/2/2020 2:30:23 PM | P | DONE |
|
|
FDC has been relocated to the Idaho St side of the building.
Mike Phone #: ###-####
|
FIR19-00489
| INSP-Sprinkler Rough-in/Hydro | 4/1/2020 | 4/2/2020 | 4/2/2020 2:16:17 PM | P | CANC |
|
|
Hydrostatic test to be rescheduled, did not get pumped up in the alotted time, this request is cancelled.
Todd Ketterling is the contact. Thanks(: Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00489
| INSP-Sprinkler Rough-in | 4/1/2020 | 4/2/2020 | 4/2/2020 2:13:16 PM | P | PART |
|
|
Rough to cover inspection for remaining overhead fire sprinkler piping in cafeteria complete, approved for cover.
Todd Ketterling is the contact. Thanks for all your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR20-00190
| INSP-Final Inspection | 4/1/2020 | 4/2/2020 | 4/2/2020 12:34:43 PM | P | PART |
|
|
Final fire sprinkler inspection for scope of work is complete, install is per NFPA13, pipe sizing is different than what was submitted, need to verify pipe sizing will work or corrections will be required.
Kenny Caldwell is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR20-00190
| INSP-Sprinkler Rough-in | 4/1/2020 | 4/2/2020 | 4/2/2020 12:29:30 PM | P | PASS |
|
|
Rough in inspection for scope of work is complete, will need to verify pipe size changes will work for application, pipe sizing is different than what was submitted.
Kenny Caldwell is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR20-00127
| INSP-Sprinkler Rough-in | 4/1/2020 | 4/2/2020 | 4/2/2020 10:43:34 AM | P | FAIL |
|
|
Notated city approved drawings that were onsite an area where the piping is in the attic space that requires tenting is to far away from heat source, relocate piping to wall cavity or provide heat calculations supporting area of install.
Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00108
| INSP-Sprinkler Rough-in | 4/1/2020 | 4/2/2020 | 4/2/2020 10:36:47 AM | P | FAIL |
|
|
Tenting not installed at time of inspection, cover is not approved.
Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR18-00346
| INSP-Final Inspection | 3/30/2020 | 4/2/2020 | 4/2/2020 9:44:37 AM | A | PASS |
|
|
Final inspection for scope of work is complete.
Please call Jake Adams ###-#### He will meet you on site with the alarm company tech and required paperwork.. Inspection requested via web by Jeff Gooch
|
FIR20-00170
| INSP-Final Inspection | 3/30/2020 | 4/2/2020 | 4/2/2020 9:44:13 AM | A | PASS |
|
|
Final inspection for scope of work is complete.
Phone #: 2082581624 >> Inspection requested via mobile web by Brandon Higley
|
FIR19-00914
| INSP-Sprinkler Rough-in/Hydro | 3/31/2020 | 4/2/2020 | 4/1/2020 9:56:16 AM | A | CANC |
|
|
Talon is the contact. Thanks!(: Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
FIR19-00914
| INSP-Sprinkler Rough-in | 3/31/2020 | 4/2/2020 | 4/1/2020 9:56:14 AM | A | CANC |
|
|
Talon is the contact. Thanks for all your help(: Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|