BLD04-01700
| FIRE-Final Inspection | 4/20/2005 | 4/20/2005 | 4/20/2005 4:48:43 PM | P | FAIL |
|
|
Two exit signs at main entrance do not operate under emergency power supply. Test and verify exit disharge lighting and outdoor listing. Provide "when building is occupied" sign and remove thumb turn from main dbl. doors. Fire ext. in billing dept. is mou
|
FIR05-00187
| INSP-Sprinkler Rough-in/Hydro | 4/20/2005 | 4/20/2005 | 4/20/2005 3:15:33 PM | P | FAIL |
|
|
Hangers on pipe supplying pendents exceeding 100 psi. static must be within 1' of the end. Some 1'' CPVC is not yet removed in basement area suite 3B furniture store. Head in basement storage room is too far below beam. Upright is blocked by copper pi
|
FIR04-00737
| INSP-Sprinkler Rough-in/Hydro | 4/19/2005 | 4/20/2005 | 4/20/2005 1:34:29 PM | P | FAIL |
|
|
Head required in entry north side for combustible concealled space. Move 4-way brace closer to change of direction on 3'' main. Flexible coupling req. on 2.5" main through floor at mech. mezz. Verify 10' length on lateral EQ bracing is sufficient. Two
|
FIR04-00627
| INSP-Sprinkler Rough-in/Hydro | 4/19/2005 | 4/20/2005 | 4/20/2005 1:24:34 PM | P | PASS |
|
|
Underground fire supply line hydro OK.
|