ELE06-01359
| Temporary Service | 4/20/2006 | 4/20/2006 | 4/20/2006 4:19:51 PM | P | FAIL |
|
|
###-#### - ed BCC address shall be posted, job id sticker shall be posted, nec 250.24(A)(1) gec shall be connected to gnded conductor terminal, fee due
|
ELE06-01352
| Final | 4/19/2006 | 4/20/2006 | 4/20/2006 4:17:53 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook called contr, could not find any t/s pole, he thought set in morning. fee due
|
ELE06-00416
| Permanent Service | 4/19/2006 | 4/20/2006 | 4/20/2006 4:16:05 PM | P | NR |
|
|
Permanent service inspection for Fire Station, Please inspect later in the afternoon, We should be ready about 3:30-4pm; Phone #: ###-#### Internet Inspection Request from: todd hall looked at some of installation, the wireway was too small, the service disconnects not ready, need another ground rod, need gec bushings on metal pipe, told to call for morning inspection if ready
|
ELE05-04507
| Permanent Service | 4/20/2006 | 4/20/2006 | 4/20/2006 4:01:48 PM | P | CANC |
|
|
justin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles addresses don' t agree with erosion control sign, is it 36th or anderson? looked at service gear and is ok, subpanels not made-up, no house panel, no outside addresses posted on bldg, no meter identification, met contr and general and told them fix and recall
|
ELE06-00049
| Final | 4/20/2006 | 4/20/2006 | 4/20/2006 3:06:04 PM | P | PASS |
|
|
degrandge; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
|
ELE06-01353
| Temporary Service | 4/20/2006 | 4/20/2006 | 4/20/2006 1:57:32 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas t/s u/g n ok
|
ELE06-01342
| Electrical Rough-In | 4/20/2006 | 4/20/2006 | 4/20/2006 12:47:44 PM | P | PASS |
|
|
lloyd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok
|
ELE06-01332
| Electrical Rough-In | 4/18/2006 | 4/20/2006 | 4/20/2006 11:37:37 AM | A | FAIL |
|
|
###-#### - steve called contr left message left corr notice, 300.4(A) &(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, BCC all make-up shall be done
|
ELE06-00084
| Final | 4/19/2006 | 4/20/2006 | 4/20/2006 10:22:45 AM | A | FAIL |
|
|
MIKE; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, 422.31(B) shall provide bkr lo for dishwasher, 430.107 motor disconnect for jetted tub shall be readily accessible, 406.5 recpt faceplates shall seat against finished surface, front room, kitchen island shall have faceplates installed, 110.3 mud room recpt shall operate, washer recpt shows bad neutral
|
ELE06-01026
| Rough-In Permanent Service | 4/20/2006 | 4/20/2006 | 4/20/2006 10:03:23 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 4/20/2006 at 7:06:25 AM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
|
ELE06-01349
| Electrical Rough-In | 4/19/2006 | 4/20/2006 | 4/20/2006 9:37:13 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 4/19/2006 at 4:05:27 PM. Contact: ###-####. walls only ok to cover
|
ELE06-00113
| Electrical Rough-In | 4/19/2006 | 4/20/2006 | 4/20/2006 8:45:45 AM | A | PART |
|
|
CONTACT: GREG PACK - ROUGH IN CEILING INSPECTION 8TH FLOOR; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ri ok clgs walls anop for 6, 7, 8, 9 floors
|
ELE06-01265
| Electrical Rough-In | 4/19/2006 | 4/20/2006 | 4/19/2006 4:45:30 PM | A | PASS |
|
|
MICHAEL; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok, corr made
|