Inspections for the day of: Thursday, April 20, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01359 Temporary Service4/20/20064/20/20064/20/2006 4:19:51 PMPFAIL
###-#### - ed BCC address shall be posted, job id sticker shall be posted, nec 250.24(A)(1) gec shall be connected to gnded conductor terminal, fee due
ELE06-01352 Final4/19/20064/20/20064/20/2006 4:17:53 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook called contr, could not find any t/s pole, he thought set in morning. fee due
ELE06-00416 Permanent Service4/19/20064/20/20064/20/2006 4:16:05 PMPNR
Permanent service inspection for Fire Station, Please inspect later in the afternoon, We should be ready about 3:30-4pm; Phone #: ###-#### Internet Inspection Request from: todd hall looked at some of installation, the wireway was too small, the service disconnects not ready, need another ground rod, need gec bushings on metal pipe, told to call for morning inspection if ready
ELE05-04507 Permanent Service4/20/20064/20/20064/20/2006 4:01:48 PMPCANC
justin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles addresses don' t agree with erosion control sign, is it 36th or anderson? looked at service gear and is ok, subpanels not made-up, no house panel, no outside addresses posted on bldg, no meter identification, met contr and general and told them fix and recall
ELE06-00049 Final4/20/20064/20/20064/20/2006 3:06:04 PMPPASS
degrandge; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
ELE06-01353 Temporary Service4/20/20064/20/20064/20/2006 1:57:32 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Joe Thomas t/s u/g n ok
ELE06-01342 Electrical Rough-In4/20/20064/20/20064/20/2006 12:47:44 PMPPASS
lloyd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok
ELE06-01332 Electrical Rough-In4/18/20064/20/20064/20/2006 11:37:37 AMAFAIL
###-#### - steve called contr left message left corr notice, 300.4(A) &(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, BCC all make-up shall be done
ELE06-00084 Final4/19/20064/20/20064/20/2006 10:22:45 AMAFAIL
MIKE; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, 422.31(B) shall provide bkr lo for dishwasher, 430.107 motor disconnect for jetted tub shall be readily accessible, 406.5 recpt faceplates shall seat against finished surface, front room, kitchen island shall have faceplates installed, 110.3 mud room recpt shall operate, washer recpt shows bad neutral
ELE06-01026 Rough-In Permanent Service4/20/20064/20/20064/20/2006 10:03:23 AMAPASS
Scheduled by a contractor via Hello! on 4/20/2006 at 7:06:25 AM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
ELE06-01349 Electrical Rough-In4/19/20064/20/20064/20/2006 9:37:13 AMAPASS
Scheduled by a contractor via Hello! on 4/19/2006 at 4:05:27 PM. Contact: ###-####. walls only ok to cover
ELE06-00113 Electrical Rough-In4/19/20064/20/20064/20/2006 8:45:45 AMAPART
CONTACT: GREG PACK - ROUGH IN CEILING INSPECTION 8TH FLOOR; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ri ok clgs walls anop for 6, 7, 8, 9 floors
ELE06-01265 Electrical Rough-In4/19/20064/20/20064/19/2006 4:45:30 PMAPASS
MICHAEL; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok, corr made