Inspections for the day of: Thursday, April 20, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00406 INSP-Alarm Testing4/20/20064/20/20064/20/2006 5:19:58 PMPCANC
Scheduled by a contractor via Hello! on 4/20/2006 at 10:07:34 AM. Contact: ###-####. To be completed early am at next scheduled inspection per conversation with contractor.
BLD04-01323 FIRE-Final Inspection4/20/20064/20/20064/20/2006 5:18:48 PMPFAIL
The project related alarm for Foster building failed inspection.
FIR05-00075 INSP-Final Inspection4/20/20064/20/20064/20/2006 5:17:13 PMPFAIL
The outside bell failed to operate upon water flow, elevator lobby smokes tested okay, tampers at the basement and 1st floor tested okay.
MIS06-00078 FIR-Final4/20/20064/20/20064/20/2006 2:06:11 PMPPASS
Correction notice items have been verified for completion, inspection passed.
BLD06-00073 FIRE-Final Inspection4/19/20064/20/20064/20/2006 12:46:02 PMPPASS
c/n items have been completed, fire life safety inspection passed.
FIR05-00285 FIR-Aging Inspection4/20/20064/20/20064/20/2006 12:42:03 PM DONE
wip
FIR06-00211 INSP-Final Inspection4/19/20064/20/20064/20/2006 12:32:22 PMPPASS
Fire sprinkler work passed final inspection.
FIR05-00878 INSP-Final Inspection4/20/20064/20/20064/20/2006 11:33:23 AMPDONE
Project has been finaled.
FIR05-00449 INSP-Alarm Testing4/19/20064/20/20064/20/2006 11:28:14 AMAPART
Tested elevator machine room, elevator shutdown/recall, FACP, phone lines, battery, obtained signal verifications. Need to provide firemans phones, remove all remaining covers at SD, add FJ at the penthouse stair landing, and provide updated map at the panel prior to final approval. Some items regarding section 509 of the IFC for the command center still need addressed including item #4, #10 and min. ft2 of the room.
FIR05-00699 INSP-Final Inspection4/19/20064/20/20064/20/2006 11:19:41 AMAPASS
Fire alarm tested satisfactory, inspection passed.