FIR06-00595
| INSP-Alarm Testing | 4/17/2007 | 4/18/2007 | | P | |
|
|
don - after 5p, said he talked to forrest; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|
FIR06-00675
| FIR-Aging Inspection | 4/20/2007 | 4/20/2007 | 4/25/2007 10:46:46 PM | | DONE |
|
|
Work in progress.
|
BLD07-00064
| FIRE-Conference | 4/19/2007 | 4/20/2007 | 4/23/2007 4:43:21 PM | P | DONE |
|
|
On site conference to discuss fire code review note items such as door hardware, exit signage and emergency lighting, hood suppression systems, etc.
|
BLD06-02887
| FIRE-Final Inspection | 4/19/2007 | 4/20/2007 | 4/20/2007 3:45:04 PM | P | PASS |
|
|
Fire life safety inspection passed.
|
FIR06-00990
| INSP-Final Inspection | 4/19/2007 | 4/20/2007 | 4/20/2007 3:02:41 PM | P | PASS |
|
|
Fire sprinkler permit finaled, inspection passed.
|
BLD05-01462
| FIRE-Final Inspection | 4/19/2007 | 4/20/2007 | 4/20/2007 2:15:21 PM | A | PART |
|
|
Final pending completion and final of the building fire alarm and sprinkler upgrade permits.
|
FIR07-00136
| INSP-Final Inspection | 4/19/2007 | 4/20/2007 | 4/20/2007 1:39:24 PM | A | PASS |
|
|
Plan resubmittals verified, final fire sprinkler inspection passed, permit finaled.
|
BLD06-02369
| FIRE-Final Inspection | 4/20/2007 | 4/20/2007 | 4/20/2007 1:03:40 PM | P | FAIL |
|
|
See correction notice on site, items include missing emergency lights and exit signs, provide correct door hardware at the second exit on the first floor, need to have project related fire alarm and sprinkler permits finaled prior to BLD life safety final.
|
FIR07-00363
| INSP-Final Inspection | 4/20/2007 | 4/20/2007 | 4/20/2007 12:58:28 PM | P | PASS |
|
|
Verified scope of fire alarm demo work has been completed, noted one remaining horn speaker which was removed while on site, demo permit finaled.
|
BLD06-03202
| FIRE-Final Inspection | 4/19/2007 | 4/20/2007 | 4/20/2007 12:55:16 PM | A | PASS |
|
|
Noted corrections to be made prior to structural final including passage hardware at the two kitchen cooking area doors, provide one a 2A10BC fire extinguisher for the cafeteria area, provide one additional exit sign as discussed.
|
BLD07-00752
| FIRE-Final Inspection | 4/19/2007 | 4/20/2007 | 4/20/2007 12:51:54 PM | A | PASS |
|
|
Fire life safety is acceptable, manual flush bolt at the main entry/exit disabled while on site.
|
FIR07-00100
| INSP-Final Inspection | 4/19/2007 | 4/20/2007 | 4/20/2007 12:47:01 PM | A | FAIL |
|
|
Provide an outside control valve as indicated on fire code review notes, also need to repair one escutcheon at the second floor atrium.
|
FIR07-00264
| INSP-Alarm Testing | 4/19/2007 | 4/20/2007 | 4/20/2007 12:45:20 PM | A | PART |
|
|
Items noted on previous c/n have been verified for compliance, final pending installation of an outside control valve supervisory switch for sprinkler monitoring as indicated on approved plans.
|