Inspections for the day of: Tuesday, April 20, 2010.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-00743 Final4/20/20104/20/20104/20/2010 3:39:31 PMPPASS
Paul ###-#### met contractor, ok to final, no esc this project
ELE10-00550 Final4/19/20104/20/20104/20/2010 3:38:44 PMPPASS
Inspection requested from web by: TOM BICANDI Phone #: ###-#### ok to final
ESC10-00070 General Inspection4/20/20104/20/20104/20/2010 3:17:39 PMPPASS
ELE10-00551 Final4/19/20104/20/20104/20/2010 3:17:00 PMPPASS
Inspection requested from web by: TOM BICANDI Phone #: ###-#### ok to final
ESC10-00076 General Inspection4/20/20104/20/20104/20/2010 2:53:04 PMPPASS
ELE09-02110 Final4/20/20104/20/20104/20/2010 2:38:00 PMPPASS
Mark ###-#### ok to final, signed card, no esc this project
ELE09-02111 Final4/20/20104/20/20104/20/2010 2:01:13 PMPCANC
Please call to meet.
Desk ###-####
Cell ###-#### Inspection requested from web by: Mark M Phone #: ###-#### wrong permit, see added inspection
ELE10-00798 Temporary Service4/20/20104/20/20104/20/2010 1:05:18 PMPPASS
Inspection requested from web by: David Oliver Phone #: ###-#### corrections made, t/s u/g n ok, no esc this project
ELE10-00743 Electrical Rough-In4/20/20104/20/20104/20/2010 12:23:22 PMPPASS
paul Phone #: ###-#### ric ok, no esc this project
ELE10-00803 Electrical Rough-In4/19/20104/20/20104/20/2010 10:31:02 AMAPASS
Please call Scott, at ###-#### 1/2 hour befor inspection for access.
Thanks
Dan Inspection requested from web by: Dan Rohl Phone #: ###-#### met contractor, asked him to call to get permits tied together, ric ok, no esc this project
ELE10-00022 Final4/19/20104/20/20104/20/2010 9:57:36 AMAFAIL
rick Phone #: ###-#### called, left correction notice, NEC 210.52(C)(4) shall provide receptacles within 2' of sink, 406.4 receptacles shall be securely mounted- kitchen, doenstairs, 110.3(B) equipment shall be installed and used per instructions- downstairs gfci, 400.8 shall not run cords thru walls, floors- downstairs closet, NOTE: corrections shall be made within 5 working days or further action will be taken
ELE10-00762 Electrical Rough-In4/19/20104/20/20104/20/2010 8:54:15 AMAPASS
Someone will be there, if you have any questions, please call Clay. Thank you. Inspection requested from web by: Clay Morgan Phone #: ###-#### ric ok, no esc this project
ELE10-00680 Electrical Rough-In4/20/20104/20/20104/20/2010 8:17:56 AMAPASS
U/G Inspection requested from web by: Mark Sessions Phone #: ###-#### ok to cover u/g in building going north towards canopy, will see outside later
ELE10-00801 Final4/20/20104/20/20104/20/2010 4:38:04 AMAPASS
Dan ###-#### ok to final, no esc this project