ELE10-00743
| Final | 4/20/2010 | 4/20/2010 | 4/20/2010 3:39:31 PM | P | PASS |
|
|
Paul ###-#### met contractor, ok to final, no esc this project
|
ELE10-00550
| Final | 4/19/2010 | 4/20/2010 | 4/20/2010 3:38:44 PM | P | PASS |
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### ok to final
|
ESC10-00070
| General Inspection | 4/20/2010 | 4/20/2010 | 4/20/2010 3:17:39 PM | P | PASS |
|
|
|
ELE10-00551
| Final | 4/19/2010 | 4/20/2010 | 4/20/2010 3:17:00 PM | P | PASS |
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### ok to final
|
ESC10-00076
| General Inspection | 4/20/2010 | 4/20/2010 | 4/20/2010 2:53:04 PM | P | PASS |
|
|
|
ELE09-02110
| Final | 4/20/2010 | 4/20/2010 | 4/20/2010 2:38:00 PM | P | PASS |
|
|
Mark ###-#### ok to final, signed card, no esc this project
|
ELE09-02111
| Final | 4/20/2010 | 4/20/2010 | 4/20/2010 2:01:13 PM | P | CANC |
|
|
Please call to meet. Desk ###-#### Cell ###-#### Inspection requested from web by: Mark M Phone #: ###-#### wrong permit, see added inspection
|
ELE10-00798
| Temporary Service | 4/20/2010 | 4/20/2010 | 4/20/2010 1:05:18 PM | P | PASS |
|
|
Inspection requested from web by: David Oliver Phone #: ###-#### corrections made, t/s u/g n ok, no esc this project
|
ELE10-00743
| Electrical Rough-In | 4/20/2010 | 4/20/2010 | 4/20/2010 12:23:22 PM | P | PASS |
|
|
paul Phone #: ###-#### ric ok, no esc this project
|
ELE10-00803
| Electrical Rough-In | 4/19/2010 | 4/20/2010 | 4/20/2010 10:31:02 AM | A | PASS |
|
|
Please call Scott, at ###-#### 1/2 hour befor inspection for access. Thanks Dan Inspection requested from web by: Dan Rohl Phone #: ###-#### met contractor, asked him to call to get permits tied together, ric ok, no esc this project
|
ELE10-00022
| Final | 4/19/2010 | 4/20/2010 | 4/20/2010 9:57:36 AM | A | FAIL |
|
|
rick Phone #: ###-#### called, left correction notice, NEC 210.52(C)(4) shall provide receptacles within 2' of sink, 406.4 receptacles shall be securely mounted- kitchen, doenstairs, 110.3(B) equipment shall be installed and used per instructions- downstairs gfci, 400.8 shall not run cords thru walls, floors- downstairs closet, NOTE: corrections shall be made within 5 working days or further action will be taken
|
ELE10-00762
| Electrical Rough-In | 4/19/2010 | 4/20/2010 | 4/20/2010 8:54:15 AM | A | PASS |
|
|
Someone will be there, if you have any questions, please call Clay. Thank you. Inspection requested from web by: Clay Morgan Phone #: ###-#### ric ok, no esc this project
|
ELE10-00680
| Electrical Rough-In | 4/20/2010 | 4/20/2010 | 4/20/2010 8:17:56 AM | A | PASS |
|
|
U/G Inspection requested from web by: Mark Sessions Phone #: ###-#### ok to cover u/g in building going north towards canopy, will see outside later
|
ELE10-00801
| Final | 4/20/2010 | 4/20/2010 | 4/20/2010 4:38:04 AM | A | PASS |
|
|
Dan ###-#### ok to final, no esc this project
|