FIR11-00144
| INSP-Final Inspection | 4/20/2011 | 4/20/2011 | 4/21/2011 3:50:10 PM | P | PASS |
|
|
Fire alarm work passed inspection. Permit finaled.
|
FIR10-00569
| INSP-Final Inspection | 4/19/2011 | 4/20/2011 | 4/21/2011 3:49:28 PM | A | NR |
|
|
Provide sprinkler coverage at the second floor patio room, records indicate an overhead hydrostatic test remains, FDC appears partially obstructed. Outside bell repaired while on site.
|
FIR11-00011
| INSP-Sprinkler Rough-in/Hydro | 4/19/2011 | 4/20/2011 | 4/20/2011 5:21:24 PM | A | PART |
|
|
Final pending relocated smoke detector at the second floor elevator, if provided- the remote annunciator needs to be adjacent to the main entry, post signage at the door to the FACP room. Remainder of installation passed inspection.
|
FIR11-00106
| INSP-Final Inspection | 4/20/2011 | 4/20/2011 | 4/20/2011 5:16:37 PM | P | PASS |
|
|
Fire alarm work passed after adjustments made while on site. Permit finaled.
|
BLD11-00307
| FIRE-Final Inspection | 4/19/2011 | 4/20/2011 | 4/20/2011 5:15:23 PM | A | PASS |
|
|
Fire life safety completed satisfactory.
|
FIR11-00107
| INSP-Final Inspection | 4/20/2011 | 4/20/2011 | 4/20/2011 5:14:39 PM | P | PASS |
|
|
Fire alarm test passed. Permit final approved.
|
FIR10-00540
| INSP-Sprinkler Rough-in | 4/19/2011 | 4/20/2011 | 4/20/2011 4:27:15 PM | A | PART |
|
|
See annotations on stamped plan set for areas on the 3rd floor okayed to cover with hard lid ceilings.
|
FIR11-00170
| INSP-Sprinkler Rough-in | 4/19/2011 | 4/20/2011 | 4/20/2011 4:25:19 PM | A | PART |
|
|
Okay to cover overhead work above areas with sheetrock ceilings as marked and clouded on approved plans. Non-sprinklered concealed spaces at three locations enclosed by combustible construction to be filled with insulation to meet exceptions allowed per NFPA 13.
|
BLD10-02982
| FIRE-Final Inspection | 4/19/2011 | 4/20/2011 | 4/20/2011 12:44:44 PM | A | FAIL |
|
|
Smoke detector at the south side did not release door hold as designed.
|
BLD11-00297
| FIRE-Final Inspection | 4/19/2011 | 4/20/2011 | 4/20/2011 12:39:18 PM | A | PASS |
|
|
Correction items finished. Fire life safety finaled.
|
FIR11-00171
| INSP-Final Inspection | 4/19/2011 | 4/20/2011 | 4/20/2011 12:36:03 PM | A | PASS |
|
|
Scope of fire sprinkler work passed field inspection. Permit finaled.
|