Inspections for the day of: Wednesday, April 20, 2011.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00144 INSP-Final Inspection4/20/20114/20/20114/21/2011 3:50:10 PMPPASS
Fire alarm work passed inspection. Permit finaled.
FIR10-00569 INSP-Final Inspection4/19/20114/20/20114/21/2011 3:49:28 PMANR
Provide sprinkler coverage at the second floor patio room, records indicate an overhead hydrostatic test remains, FDC appears partially obstructed. Outside bell repaired while on site.
FIR11-00011 INSP-Sprinkler Rough-in/Hydro4/19/20114/20/20114/20/2011 5:21:24 PMAPART
Final pending relocated smoke detector at the second floor elevator, if provided- the remote annunciator needs to be adjacent to the main entry, post signage at the door to the FACP room. Remainder of installation passed inspection.
FIR11-00106 INSP-Final Inspection4/20/20114/20/20114/20/2011 5:16:37 PMPPASS
Fire alarm work passed after adjustments made while on site. Permit finaled.
BLD11-00307 FIRE-Final Inspection4/19/20114/20/20114/20/2011 5:15:23 PMAPASS
Fire life safety completed satisfactory.
FIR11-00107 INSP-Final Inspection4/20/20114/20/20114/20/2011 5:14:39 PMPPASS
Fire alarm test passed. Permit final approved.
FIR10-00540 INSP-Sprinkler Rough-in4/19/20114/20/20114/20/2011 4:27:15 PMAPART
See annotations on stamped plan set for areas on the 3rd floor okayed to cover with hard lid ceilings.
FIR11-00170 INSP-Sprinkler Rough-in4/19/20114/20/20114/20/2011 4:25:19 PMAPART
Okay to cover overhead work above areas with sheetrock ceilings as marked and clouded on approved plans. Non-sprinklered concealed spaces at three locations enclosed by combustible construction to be filled with insulation to meet exceptions allowed per NFPA 13.
BLD10-02982 FIRE-Final Inspection4/19/20114/20/20114/20/2011 12:44:44 PMAFAIL
Smoke detector at the south side did not release door hold as designed.
BLD11-00297 FIRE-Final Inspection4/19/20114/20/20114/20/2011 12:39:18 PMAPASS
Correction items finished. Fire life safety finaled.
FIR11-00171 INSP-Final Inspection4/19/20114/20/20114/20/2011 12:36:03 PMAPASS
Scope of fire sprinkler work passed field inspection. Permit finaled.