Inspections for the day of: Wednesday, April 20, 2011.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00263 FIR-Aging Inspection4/20/20114/20/20114/27/2011 9:30:43 AM DEFR
FIR08-00367 FIR-Aging Inspection4/20/20114/20/20114/27/2011 9:30:18 AM NR
Per Brian work on this project is in progress. Apparently the wiring on the NAC circuits is incorrect.
FIR11-00094 INSP-Final Inspection4/20/20114/20/20114/20/2011 4:25:16 PMPCANC
canceled due to time constraints. rescheduled for tomorrow.
BLD11-00058 FIRE-Final Inspection4/20/20114/20/20114/20/2011 4:24:43 PMPCANC
canceled due to time constraints. rescheduled for tomorrow.
FIR08-00550 INSP-Final Inspection4/18/20114/20/20114/20/2011 4:18:57 PMPFAIL
Neither the strobes or the horn were syncronized. Also need to test all initiating devices. Candella needs to be modified to 110cd on the strobe in the old engineering office. End of Line voltage was verified ok as well as spacing of the manual pull stations and audio/visual devices. Netcon was also verified at 5.
BLD10-01256 FIRE-Final Inspection4/19/20114/20/20114/20/2011 3:34:47 PMPFAIL
Life safety will be able to be finaled when the exit discharge light at the east exit door is repaired.
FIR11-00130 INSP-Sprinkler Rough-in4/19/20114/20/20114/20/2011 1:36:01 PMAPASS
The remaining underground supply piping can be covered.
BLD11-00375 FIRE-Final Inspection4/20/20114/20/20114/20/2011 11:35:19 AMAFAIL
The exit sign failed to switch to battery backup when tested. Per Darren the hole in the wall that provides access to the area over the patio area will be patched.
BLD10-02915 FIRE-Final Inspection4/19/20114/20/20114/20/2011 10:11:01 AMAPASS
life safety passed. Per conversation with the building inspector the west facing exit doors that require the single action hardware will be verified by the building inspector.
BLD11-00578 FIRE-Final Inspection4/18/20114/20/20114/20/2011 8:30:26 AMAPASS
life safety passed