FIR09-00263
| FIR-Aging Inspection | 4/20/2011 | 4/20/2011 | 4/27/2011 9:30:43 AM | | DEFR |
|
|
|
FIR08-00367
| FIR-Aging Inspection | 4/20/2011 | 4/20/2011 | 4/27/2011 9:30:18 AM | | NR |
|
|
Per Brian work on this project is in progress. Apparently the wiring on the NAC circuits is incorrect.
|
FIR11-00094
| INSP-Final Inspection | 4/20/2011 | 4/20/2011 | 4/20/2011 4:25:16 PM | P | CANC |
|
|
canceled due to time constraints. rescheduled for tomorrow.
|
BLD11-00058
| FIRE-Final Inspection | 4/20/2011 | 4/20/2011 | 4/20/2011 4:24:43 PM | P | CANC |
|
|
canceled due to time constraints. rescheduled for tomorrow.
|
FIR08-00550
| INSP-Final Inspection | 4/18/2011 | 4/20/2011 | 4/20/2011 4:18:57 PM | P | FAIL |
|
|
Neither the strobes or the horn were syncronized. Also need to test all initiating devices. Candella needs to be modified to 110cd on the strobe in the old engineering office. End of Line voltage was verified ok as well as spacing of the manual pull stations and audio/visual devices. Netcon was also verified at 5.
|
BLD10-01256
| FIRE-Final Inspection | 4/19/2011 | 4/20/2011 | 4/20/2011 3:34:47 PM | P | FAIL |
|
|
Life safety will be able to be finaled when the exit discharge light at the east exit door is repaired.
|
FIR11-00130
| INSP-Sprinkler Rough-in | 4/19/2011 | 4/20/2011 | 4/20/2011 1:36:01 PM | A | PASS |
|
|
The remaining underground supply piping can be covered.
|
BLD11-00375
| FIRE-Final Inspection | 4/20/2011 | 4/20/2011 | 4/20/2011 11:35:19 AM | A | FAIL |
|
|
The exit sign failed to switch to battery backup when tested. Per Darren the hole in the wall that provides access to the area over the patio area will be patched.
|
BLD10-02915
| FIRE-Final Inspection | 4/19/2011 | 4/20/2011 | 4/20/2011 10:11:01 AM | A | PASS |
|
|
life safety passed. Per conversation with the building inspector the west facing exit doors that require the single action hardware will be verified by the building inspector.
|
BLD11-00578
| FIRE-Final Inspection | 4/18/2011 | 4/20/2011 | 4/20/2011 8:30:26 AM | A | PASS |
|
|
life safety passed
|