Inspections for the day of: Friday, April 20, 2012.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-00056 ELE-Aging Inspection4/20/20124/20/20124/27/2012 7:32:49 AM CANC
ELE10-01718 ELE-Aging Inspection4/20/20124/20/20124/27/2012 7:32:40 AM CANC
ELE11-01821 ELE-Aging Inspection4/20/20124/20/20124/27/2012 7:32:32 AM CANC
ELE10-01674 ELE-Aging Inspection4/20/20124/20/20124/24/2012 7:48:37 AM DONE
ELE12-00651 Conference4/20/20124/20/20124/20/2012 3:55:21 PMPDONE
phone conference T&B hub not listed for grding and bonding NEC 250.90,91,92, also shall correct violation of common neutrals asap
ELE12-00651 Final4/20/20124/20/20124/20/2012 3:53:25 PMPCANC
ELE12-00627 Electrical Rough-In4/20/20124/20/20124/20/2012 3:31:04 PMPPASS
Ceiling Inspection Phone #: ###-#### >> Inspection requested via web by Celinda Winters
ELE12-00830 Electrical Rough-In4/20/20124/20/20124/20/2012 3:30:54 PMPPASS
Chris ###-####
ELE12-00634 Final4/19/20124/20/20124/20/2012 11:46:43 AMAPASS
bob Phone #: ###-#### ok
ELE12-00644 Final4/19/20124/20/20124/20/2012 11:46:24 AMAPASS
Access code is 2601, thx Phone #: ###-#### >> Inspection requested via web by Stephen Kren
ELE12-00814 Permanent Service4/19/20124/20/20124/20/2012 10:26:00 AMAFAIL
Inspect 100 Amp Meter/Main Service Panel on south of residence. Lock Box code is #3350
Tim ###-#### Phone #: ###-#### >> Inspection requested via web by Tim Lawrence called correction posted
250.52(A)(1) & 104(A)(1) grd, bond water system to p/s not subpanel, 110.3(B) use onlt manufactures listed breakers,110 26 provide required clearence subpanels, address wiring in garage, needs 4 wire circuits , recepts, and pigtails to range and dryer, shall not use cord for fixed wiring 400.7&8 uses permitted and not permitted
ELE11-01362 Final4/19/20124/20/20124/20/2012 10:15:40 AMAPASS
thanks...see you tomorrow.
Gene
Jonese Electric Phone #: ###-#### >> Inspection requested via web by Gene Jones
ELE10-01512 DOC - Permit Finaled4/20/20124/20/20124/20/2012 8:14:04 AMAPASS
job was finaled