FIR11-00344
| INSP-Conference | 4/20/2012 | 4/20/2012 | 4/20/2012 3:27:29 PM | P | DONE |
|
|
Art and I discussed what I would need to complete the inspection for this project.
|
FIR11-00472
| INSP-Conference | 4/20/2012 | 4/20/2012 | 4/20/2012 3:14:16 PM | P | DONE |
|
|
Art and I discussed what I would need to complete the inspection for this project.
|
FIR11-00638
| INSP-Sprinkler Rough-in | 4/20/2012 | 4/20/2012 | 4/20/2012 2:55:44 PM | P | DONE |
|
|
Lonnie had concerns over the two beams blocking pendant sprinkler coverage in the "Great Room". I met the general contractor and showed him the obstruction charts in NFPA 13D. It appears that the best option is three addtional heads in the center beam pocket.
|
BLD12-00491
| FIRE-Final Inspection | 4/19/2012 | 4/20/2012 | 4/20/2012 12:58:09 PM | A | FAIL |
|
|
Provide annual inspection for the fire extinguisher, install doors and harware for verification, reverse door swing for the common restroom corridor per the approved plans, provide suite number.
|
FIR12-00168
| INSP-Sprinkler Rough-in | 4/19/2012 | 4/20/2012 | 4/20/2012 11:21:27 AM | A | PASS |
|
|
Sprinkler piping is ok to cover
|