BLD15-00408
| FIRE-Final Inspection | 4/20/2015 | 4/20/2015 | 4/20/2015 3:46:36 PM | P | FAIL |
|
|
Provide single action hardware for the new restroom door and provide fire extinguishers as discussed for the rest of the business.
|
FIR14-00619
| INSP-Sprinkler Rough-in/Hydro | 4/20/2015 | 4/20/2015 | 4/20/2015 3:23:41 PM | P | CANC |
|
|
Overbooked will need to reschedule
|
FIR14-00622
| INSP-Sprinkler Rough-in/Hydro | 4/20/2015 | 4/20/2015 | 4/20/2015 3:22:30 PM | P | CANC |
|
|
Overbooked. Will need to reschedule
|
FIR14-00620
| INSP-Sprinkler Rough-in/Hydro | 4/20/2015 | 4/20/2015 | 4/20/2015 3:20:44 PM | P | CANC |
|
|
Overbooked will need to reschedule
|
FIR14-00765
| INSP-Sprinkler Rough-in | 4/17/2015 | 4/20/2015 | 4/20/2015 3:18:46 PM | A | PASS |
|
|
Tenting inspection passed. Piping can be covered.
|
FIR15-00082
| INSP-Sprinkler Rough-in/Hydro | 4/20/2015 | 4/20/2015 | 4/20/2015 2:44:41 PM | P | PASS |
|
|
Second floor hydro test passed
|
FIR15-00171
| INSP-Sprinkler Rough-in | 4/20/2015 | 4/20/2015 | 4/20/2015 2:16:15 PM | P | PASS |
|
|
Piping as marked "ok" is ok to cover.
|
BLD13-00166
| FIRE-Final Inspection | 4/17/2015 | 4/20/2015 | 4/20/2015 1:39:25 PM | A | FAIL |
|
|
Provide single action hardware on the new doors, provide annual inspection for all fire extinguishers, repair exit sign at the corridor end in the new area, provide/extend the existing fire alarm system into the new area (this includes all rooms/corridors).
|
FIR13-00612
| INSP-Final Inspection | 4/17/2015 | 4/20/2015 | 4/20/2015 1:31:55 PM | P | CANC |
|
|
Cancel per Robert
|
BLD15-00167
| FIRE-Final Inspection | 4/17/2015 | 4/20/2015 | 4/20/2015 1:07:47 PM | A | CANC |
|
|
Could not make it at the same time as Beverly Phone #: ###-####
|
BLD14-02350
| FIRE-Final Inspection | 4/15/2015 | 4/20/2015 | 4/20/2015 10:26:31 AM | A | FAIL |
|
|
Life safety ok to pass when the project related fire sprinkler and fire alarm permits are passed.
|
FIR14-00238
| INSP-Final Inspection | 4/20/2015 | 4/20/2015 | 4/20/2015 10:25:20 AM | P | FAIL |
|
|
Missing remote annunciator, missing document box. Did not test devices due to the missing remote annunciator.
|
FIR14-00923
| INSP-Final Inspection | 4/17/2015 | 4/20/2015 | 4/20/2015 10:19:58 AM | A | PART |
|
|
Forward flush passed. Could not test flows and tampers due to fire alarm issues.
|
FIR14-00824
| INSP-Final Inspection | 4/19/2015 | 4/20/2015 | 4/20/2015 10:09:11 AM | A | FAIL |
|
|
Need to provide correct height for the exterior strob on roof and all emergency lights prior to a final sign off.. All other items tested ok.
|
FIR14-00764
| INSP-Sprinkler Rough-in | 4/17/2015 | 4/20/2015 | 4/20/2015 12:00:00 AM | A | DONE |
|
|
Brian tinting Phone #: ###-####
|