BLD14-03175
| FIRE-Final Inspection | 4/20/2016 | 4/20/2016 | 4/20/2016 3:14:07 PM | P | CANC |
|
|
Inspection request cancelled, cannot complete life fire safety inspection with FIR permit for alarms still in issued status. Fire alarm permit needs to be inspected/finaled before life fire safety inspection can be completed and finaled.
|
FIR15-00770
| INSP-Sprinkler Rough-in | 4/20/2016 | 4/20/2016 | 4/20/2016 3:11:12 PM | P | PART |
|
|
Rough to cover inspection complete for entire building, 1st floor piping that is not in attic spaces approved for cover. 2nd level/attic (1st floor garages, garage stairways) space fire sprinkler piping rough to cover inspection complete, these area's cannot be covered until tenting inspection is completed and approved.
|
FIR15-00770
| INSP-Sprinkler Rough-in/Hydro | 4/20/2016 | 4/20/2016 | 4/20/2016 3:05:11 PM | P | PASS |
|
|
Hydrostatic test for overhead fire sprinkler piping complete for 1st and 2nd levels.
|
BLD16-01294
| FIRE-Final Inspection | 4/20/2016 | 4/20/2016 | 4/20/2016 1:22:06 PM | P | FAIL |
|
|
Building manager needs to provide documentation showing that the fire alarm system has had an annual inspection performed. Fire extinguishers need to be installed throughout the tenant space. Tenant will schedule inspection request when noted items are addressed.
|