FIR04-00024
| INSP-Sprinkler Rough-in/Hydro | 4/20/2004 | 4/21/2004 | 4/21/2004 12:00:00 AM | A | FAIL |
|
|
Resubmitted plans still do not match pipe sizing or layout of what has been installed. One area includes a remote area. See revised city plans for locations of problems. Upright heads in the attic along the east wall are spaced too far off of the wall since existing insulation does not fill the combustible space along the wall. Add insulation or sprinkler heads. There is a combustible cavity above the attic space that requires protection. Inspection stopped at locaton shown on plans. 4/21/2004 9:46:03 AM
|
MIS04-00111
| FIR-Final | 4/20/2004 | 4/21/2004 | 4/21/2004 12:00:00 AM | A | FAIL |
|
|
Actual suite numbers do not match what is shown on the plans. Provide updated address to city addressing dept. to have issue clarified. 4/21/2004 2:49:06 PM
|
BLD04-00259
| FIRE-Final Inspection | 4/20/2004 | 4/21/2004 | 4/21/2004 12:00:00 AM | A | FAIL |
|
|
Classroom 114 and Observaton rooms are ok to occupy. Area D and access controlled egress doors need to be addressed. Second floor egress issues have been corrected. 4/21/2004 10:40:40 AM
|
FIR04-00151
| INSP-Final Inspection | 4/21/2004 | 4/21/2004 | 4/21/2004 12:00:00 AM | P | FAIL |
|
|
mount map, shut down all hvac units upon activation of a duct smoke detector, monitoring company did not receive all of the signals and what they did receive was not right, (all devices need retested), verify a/v locations, mount knox box and provide signage on riser room door. Get nfpa 72 forms 4/21/2004 4:34:05 PM
|
FIR04-00213
| INSP-Final Inspection | 4/20/2004 | 4/21/2004 | 4/21/2004 12:00:00 AM | P | FAIL |
|
|
Provide the minimum 1" clearance between the upright deflector and the insulation, provide earthquake bracing on the existing sprinkler mains, pendants in the center of the retail space are overspaced. This inspection was for the retail space only. 4/21/2004 3:39:14 PM
|
MIS04-00112
| FIR-Final | 4/20/2004 | 4/21/2004 | 4/21/2004 12:00:00 AM | P | FAIL |
|
|
Actual suite numbers do not match what is shown on the plans. Provide updated address to city addressing dept. to have issue clarified. 4/21/2004 2:49:13 PM
|
FIR03-00750
| INSP-Final Inspection | 4/19/2004 | 4/21/2004 | 4/21/2004 12:00:00 AM | P | FAIL |
|
|
Provide a/v's in the two offices upstairs and storage room 130 and in the office not shown in classroom 136. These areas can be considered common areas. This may require resubmittals. 4/21/2004 3:17:21 PM
|