Inspections for the day of: Friday, April 21, 2006.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00240 ELE-Aging Inspection4/21/20064/21/20064/28/2006 12:21:25 PM FAIL
corr. called 600.5(C)(3)&410.15(B) will meet contractor 05-01-06 9:00 am
ELE05-04208 ELE-Aging Inspection4/21/20064/21/20064/27/2006 3:10:41 PM PART
wsuc could not locate new sign not installed yet ?
ELE06-01264 Final4/20/20064/21/20064/21/2006 4:18:26 PMPPASS
I need the 4 new condensing units inspected. Located behind the apartments. Danny ###-#### Thanks; Phone #: ###-#### Internet Inspection Request from: danny pugil
ELE06-01387 Rough-In Permanent Service4/21/20064/21/20064/21/2006 3:47:26 PMPPASS
###-#### partial r/i for under floor , p/s o/h rec. ok
ELE06-01344 Final4/19/20064/21/20064/21/2006 2:59:52 PMPPASS
need final inspection on new 200 amp service. new circuit for a/c & furnace. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok
ELE06-01344 Permanent Service4/21/20064/21/20064/21/2006 2:59:35 PMPPASS
NEED FINAL INSPECTION ON NEW 200 AMP SERVICE. ADD CIRCUIT FOR A/C & FURNACE. THANK YOU.; Phone #: ###-#### x Internet Inspection Request from: BRIAN KEITH
r/i ok p/s u/g rec. ok
ELE06-00407 Final4/21/20064/21/20064/21/2006 2:45:44 PMPPASS
Scheduled by a contractor via Hello! on 4/21/2006 at 9:25:45 AM. Contact: ###-####. ok card signed
ELE06-01340 Permanent Service4/21/20064/21/20064/21/2006 2:17:02 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Justin Metcalf corr. called 250.52,104 (A)(1) grd or bond water, T310.15(B)(2)a derate wires in 2" at 50%,250.64(E) use listed conn. for GEC at p/s, 300.10 bond bushing for RE washers, 250.66 GEC and bonding shall be #4 copper, 230.24 clearence over patio cover, 408.4 panel schedule, 220.55 table 40 amp circuit and wire for range 310.8(D) sunkight resistant wire at whetherhead
ELE06-01364 Electrical Rough-In4/20/20064/21/20064/21/2006 12:36:33 PMPFAIL
###-#### - rod corr. met electrician, 314.16 box fill, 210.52(A&B) outlet spacing din rm also shall be on small appliance branch circuit, 314.17 shall replace 3 gang cutin box with broken out clamps
ELE06-01368 Electrical Rough-In4/20/20064/21/20064/21/2006 11:06:52 AMAFAIL
###-#### - vivian Note: shop corr. called 300.4 nail plates, 314.17 staple romex within 8", 250.32 needs GEC to rebar at shop, needs uncover u/g covered before inspection, and update permit for 2rms, p/s
ELE06-01345 Rough-In Permanent Service4/20/20064/21/20064/21/2006 11:04:55 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung r/i ok p/s u/g new ok
ELE06-01385 Permanent Service4/21/20064/21/20064/21/2006 10:47:30 AMPCANC
###-#### contractor called and canceled
ELE06-01372 Final4/20/20064/21/20064/21/2006 10:13:41 AMAPASS
ELE06-01372 Electrical Rough-In4/20/20064/21/20064/21/2006 10:13:28 AMAPASS
allen ###-####
ELE06-00422 Electrical Rough-In4/20/20064/21/20064/21/2006 9:39:03 AMAPART
Scheduled by a contractor via Hello! on 4/20/2006 at 11:32:33 AM. Contact: ###-####. wiring in 3 counter walls, border tiles in north half of 2nd floor ok only
ELE06-00628 Rough-In Permanent Service4/21/20064/21/20064/21/2006 8:38:49 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corr. called 300.4 needs nail plates, 334.30,314.17 staple romex within 8" of boxes,250.70 use acorn or listed pipe grd clamp for GEC at rebar loose, 250.64(C) shall not splice GEC