ELE06-00238
| ELE-Aging Inspection | 4/21/2006 | 4/21/2006 | 4/26/2006 3:06:13 PM | | DONE |
|
|
see final
|
ELE06-01375
| Electrical Rough-In | 4/21/2006 | 4/21/2006 | 4/21/2006 4:28:47 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 4/21/2006 at 8:57:14 AM. Contact: ###-####. called contr, left corr notice on front glass, nec 362.30 ent shall be strapped within 3' of box and every 3', 330.30(B) mc cable shall be strapped within 12" of box, 300.4(D) ent shall be 1 1/4" from edge of framing member, 110(F)(1)(a) space equal to width and depth of panel is dedicated from floor to 6' above or structural ceiling- no foreign systems shall be in this space
|
ELE06-01388
| Temporary Service | 4/21/2006 | 4/21/2006 | 4/21/2006 4:11:12 PM | P | FAIL |
|
|
greg ###-#### called, left message,left corr notice, nec 230.24(B)(5) service drop conductors shall have minimum 18' clearance from grade over alley, 230.24(A) service drop conductors shall be minimum 8' over roof of building,250.24 grounding electrode conductor shall be connected to grounded conductor terminal, job id sticker shall be filled out, Note: this looks like homeowner permit, but temp pole has TDR lettering.All permits appear to be homeowners.
|
ELE06-01332
| Rough-In Permanent Service | 4/20/2006 | 4/21/2006 | 4/21/2006 3:47:05 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 4/20/2006 at 2:18:39 PM. Contact: ###-####. corrections not made, fee due
|
ELE06-00413
| Final | 4/20/2006 | 4/21/2006 | 4/21/2006 3:06:25 PM | P | PASS |
|
|
###-#### - eric Note: please call for access number ok to final
|
ELE06-00600
| Final | 4/21/2006 | 4/21/2006 | 4/21/2006 2:12:23 PM | P | PASS |
|
|
###-#### - aaron called contr to change a/c bkr, ok to final
|
ELE05-04395
| Final | 4/21/2006 | 4/21/2006 | 4/21/2006 1:42:43 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: TJ Sturges corr made, ok to final
|
ELE05-02758
| Final | 4/14/2006 | 4/21/2006 | 4/21/2006 12:50:06 PM | A | NH |
|
|
We:1)installed 1 new GFCI protected receptacle below the panel in the garage, and 1 new GFCI protected receptacle next to the back door switch in the garage. 2)installed 1 new weatherproof GFCI protected receptacle on the back of the house. 3)installed a new receptacle under the sink for the insta-hot on a new circuit.(#5070743strader).This work was done on 7/21/05 but customer would not schedule until now. Thanks!!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell called contr, tried 3x to find owner at home. said to call later
|
ELE06-00084
| Final | 4/21/2006 | 4/21/2006 | 4/21/2006 10:42:05 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 4/21/2006 at 7:22:14 AM. Contact: ###-####. corr made, ok to final
|
ELE06-00745
| Electrical Rough-In | 4/20/2006 | 4/21/2006 | 4/21/2006 10:16:51 AM | A | CANC |
|
|
late am; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung homeowner not doing work, called 324, wrote correction notice , posted stop work, told owner permit voided, they have 3 days to get electrical contractor or further action will be taken, i.e. possibly turn off power
|
ELE06-00400
| Final | 4/20/2006 | 4/21/2006 | 4/21/2006 9:20:02 AM | A | PASS |
|
|
###-#### - eric Note: please call access code ok to final
|
ELE06-01375
| Rough-In Permanent Service | 4/20/2006 | 4/21/2006 | 4/21/2006 8:42:51 AM | A | NH |
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook called contr, told to call when accessible
|
ELE06-01341
| Electrical Rough-In | 4/20/2006 | 4/21/2006 | 4/21/2006 8:25:24 AM | A | CANC |
|
|
bill; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met owner, and contr, no approved set of plans, told could not give inspection
|