Inspections for the day of: Friday, April 21, 2006.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00075 INSP-Final Inspection4/21/20064/21/20064/24/2006 3:13:18 PMPPASS
Permit finaled
FIR05-00520 INSP-Final Inspection4/21/20064/21/20064/21/2006 3:35:38 PMPPASS
Permit finaled
BLD05-01566 FIRE-Final Inspection4/20/20064/21/20064/21/2006 1:47:52 PMAFAIL
marlena or dave; Phone #: ###-#### Need to provide panic hardware on the inactive leaf and tag the fire extinguisher as previously listed on the previous correction notice.
FIR06-00268 INSP-Sprinkler Rough-in/Hydro4/20/20064/21/20064/21/2006 12:10:37 PMAFAIL
The new sprinkler pendant has been added to an existing 1" drop, which means there are two heads being piped from a single 1" outlet. This new head needs to be fed from the 1 1/4" branchline piping as discussed or provide hydraulic calculations.
BLD05-00545 FIRE-Final Inspection4/20/20064/21/20064/21/2006 10:59:50 AMACANC
chris; Phone #: ###-#### Per contractor he was not prepared for the sprinkler inspection and would just reschedule for next week.
FIR06-00173 INSP-Final Inspection4/21/20064/21/20064/21/2006 10:52:52 AMPPASS
Permit finaled.
BLD05-02923 FIRE-Sprinkler Rough-in4/20/20064/21/20064/21/2006 8:55:37 AMAPASS
Fire life safety finaled.