FIR06-00075
| INSP-Final Inspection | 4/21/2006 | 4/21/2006 | 4/24/2006 3:13:18 PM | P | PASS |
|
|
Permit finaled
|
FIR05-00520
| INSP-Final Inspection | 4/21/2006 | 4/21/2006 | 4/21/2006 3:35:38 PM | P | PASS |
|
|
Permit finaled
|
BLD05-01566
| FIRE-Final Inspection | 4/20/2006 | 4/21/2006 | 4/21/2006 1:47:52 PM | A | FAIL |
|
|
marlena or dave; Phone #: ###-#### Need to provide panic hardware on the inactive leaf and tag the fire extinguisher as previously listed on the previous correction notice.
|
FIR06-00268
| INSP-Sprinkler Rough-in/Hydro | 4/20/2006 | 4/21/2006 | 4/21/2006 12:10:37 PM | A | FAIL |
|
|
The new sprinkler pendant has been added to an existing 1" drop, which means there are two heads being piped from a single 1" outlet. This new head needs to be fed from the 1 1/4" branchline piping as discussed or provide hydraulic calculations.
|
BLD05-00545
| FIRE-Final Inspection | 4/20/2006 | 4/21/2006 | 4/21/2006 10:59:50 AM | A | CANC |
|
|
chris; Phone #: ###-#### Per contractor he was not prepared for the sprinkler inspection and would just reschedule for next week.
|
FIR06-00173
| INSP-Final Inspection | 4/21/2006 | 4/21/2006 | 4/21/2006 10:52:52 AM | P | PASS |
|
|
Permit finaled.
|
BLD05-02923
| FIRE-Sprinkler Rough-in | 4/20/2006 | 4/21/2006 | 4/21/2006 8:55:37 AM | A | PASS |
|
|
Fire life safety finaled.
|