Inspections for the day of: Monday, April 21, 2008.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00309 Permanent Service4/21/20084/21/20084/21/2008 4:01:01 PMPCANC
Ryan Phone #: ###-#### see conference
ELE08-00309 Conference4/21/20084/21/20084/21/2008 4:00:48 PMPDONE
Ryan Phone #: ###-#### told contractor that address still seems to be problem based on BLD, service is on , but told contractor that transformer is where service starts for low voltage part, that grounding shall be at transformer secondary, and that 800A panel shall be 4-wire with ground and grounded conductor separated
ELE08-00993 Electrical Rough-In4/21/20084/21/20084/21/2008 3:31:33 PMPPASS
PAUL CALL PRIOR TO HEADING TO SITE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy told contractor to verify BLD number, wall only ok to cover
ELE08-00738 Electrical Rough-In4/18/20084/21/20084/21/2008 2:45:21 PMPPASS
rob Phone #: ###-#### stud walls only ok to cover anop
ELE07-03761 Final4/21/20084/21/20084/21/2008 2:21:30 PMPPASS
Scheduled by a contractor via Hello! on 4/21/2008 at 8:19:06 AM. Contact: ###-####. ok to final
ELE08-00298 Final4/21/20084/21/20084/21/2008 1:43:05 PMPPASS
Scheduled by a contractor via Hello! on 4/21/2008 at 8:17:45 AM. Contact: ###-####. ok to final
ELE08-00053 Final4/21/20084/21/20084/21/2008 12:33:59 PMPPASS
call 30 min if possible before insp -dave rodell Phone #: ###-#### called contractor, signed occupancy card, ok to final
ELE04-03088 Final4/21/20084/21/20084/21/2008 11:12:43 AMPPASS
loren Phone #: ###-#### correction made, ok to final
ELE08-00900 Electrical Rough-In4/18/20084/21/20084/21/2008 10:35:11 AMACANC
Scheduled by a contractor via Hello! on 4/18/2008 at 2:53:20 PM. Contact: ###-####. contractor called, asked to cancel
ELE08-00979 Temporary Service4/18/20084/21/20084/21/2008 10:20:25 AMAPASS
W Douglas is off of W Bethel, off of Orchard and Franklin. Phone #: ###-#### Internet Inspection Request from: Stephen Kren t/s u/g n ok
ELE08-00977 Temporary Service4/18/20084/21/20084/21/2008 10:05:59 AMAPASS
W Douglas is off of W Bethel, off of Orchard and Franklin. Phone #: ###-#### Internet Inspection Request from: Stephen Kren t/s u/g n ok
ELE08-00976 Temporary Service4/18/20084/21/20084/21/2008 9:50:22 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Stephen Kren t/s u/g n ok
ELE08-00978 Temporary Service4/18/20084/21/20084/21/2008 9:33:24 AMAPASS
W Douglas is off of W Bethel, off of Orchard and Franklin. Phone #: ###-#### Internet Inspection Request from: Stephen Kren t/s u/g n ok
ELE08-00985 Rough-In Permanent Service4/18/20084/21/20084/21/2008 9:30:07 AMAPASS
Permanent service too, please. JW is Vince, ###-####. Phone #: ###-#### Internet Inspection Request from: BRENDA HURST ri ok, p/s u/g n ok
ELE08-00975 Permanent Service4/18/20084/21/20084/21/2008 8:40:54 AMAFAIL
george Phone #: ###-#### called, NEC 110.26(A)(2) width of working space shall be 30", 110.26(A)(3) work space shall be clear from grade up to height required per 110.26(E)-no water piping or low voltage allowed in space
ELE08-00734 Electrical Rough-In4/18/20084/21/20084/21/2008 8:01:42 AMAPASS
1st A.M.if possible, approval to cover outside of exterior wall owner is replacing siding and we ran 2 new wires. Phone #: ###-#### Internet Inspection Request from: Alan Lusk called contractor, ric ok for siding