BLD07-02809
| FIRE-Final Inspection | 4/21/2008 | 4/21/2008 | 4/21/2008 5:28:14 PM | P | FAIL |
|
|
Missing suite address numbers, provide max. occupant load signs per review notes, provide approved door hardware at the balcony/patio doors, missing EM lighting and exit signs at various locations, provide signage at the door the the fire riser room, remove the curtain blocking the SE kitchen exit door, storage at the kitchen areas to remain below 18" from the sprinkler deflector.
|
FIR07-01045
| INSP-Final Inspection | 4/21/2008 | 4/21/2008 | 4/21/2008 5:20:40 PM | P | PASS |
|
|
Fire alarm testing passed field inspection per K.R. NOTE: As-builts reflecting four additional duct detectors to be provided as agreed.
|
BLD07-03090
| FIRE-Final Inspection | 4/21/2008 | 4/21/2008 | 4/21/2008 5:18:55 PM | P | FAIL |
|
|
Door hardware is not approved as installed.
|
FIR08-00127
| INSP-Final Inspection | 4/21/2008 | 4/21/2008 | 4/21/2008 5:18:11 PM | P | PASS |
|
|
Fire alarm testing passed per K.R permit finaled.
|
FIR08-00267
| INSP-Final Inspection | 4/21/2008 | 4/21/2008 | 4/21/2008 5:17:06 PM | P | PASS |
|
|
Hood suppression system functioned properly under test conditions, permit finaled per K.R.
|
FIR08-00118
| INSP-Final Inspection | 4/18/2008 | 4/21/2008 | 4/21/2008 3:03:24 PM | P | CANC |
|
|
Inspection rescheduled for 4/22 per discussion.
|
FIR06-00535
| INSP-Final Inspection | 4/18/2008 | 4/21/2008 | 4/21/2008 3:02:31 PM | P | CANC |
|
|
Rescheduled per conversation with contractor.
|
BLD07-02764
| FIRE-Final Inspection | 4/21/2008 | 4/21/2008 | 4/21/2008 2:46:38 PM | P | FAIL |
|
|
Storage at the basement level mechanical crawl space is not allowed- need to remove construction materials (paint, carpet, etc. from this area), the provided fire extinguishers are mounted too high and are missing the required current inspection/certification tags-see fire code review notes for stipulations, repair the non-functional EM light at the basement rated stair enclosure, door hardware at the 2nd floor and basement level offices and restrooms must be approved.
|
BLD08-00440
| FIRE-Final Inspection | 4/18/2008 | 4/21/2008 | 4/21/2008 1:57:03 PM | A | FAIL |
|
|
Exit signs at three locations are not functional on battery backup power, missing approved door hardware at the remodeled rooms and areas.
|
BLD08-00076
| FIRE-Final Inspection | 4/21/2008 | 4/21/2008 | 4/21/2008 12:56:21 PM | P | PASS |
|
|
Fire life safety inspection passed.
|
FIR08-00048
| INSP-Final Inspection | 4/18/2008 | 4/21/2008 | 4/21/2008 12:09:31 PM | A | PASS |
|
|
Fire sprinkler permit work passed final inspection.
|
FIR07-00958
| INSP-Final Inspection | 4/18/2008 | 4/21/2008 | 4/21/2008 12:05:20 PM | A | FAIL |
|
|
Pendent head deflector at a storage closet is cut above the drop ceiling and missing escutcheon, noted the need to maintain 18" clearance to storage below sprinkler heads at the kitchen areas.
|
BLD08-00161
| FIRE-Final Inspection | 4/17/2008 | 4/21/2008 | 4/21/2008 12:01:23 PM | A | PASS |
|
|
Life safety inspection passed, one duct detector vent tube install corrected while on site.
|
BLD07-03264
| FIRE-Final Inspection | 4/18/2008 | 4/21/2008 | 4/21/2008 11:58:55 AM | A | PASS |
|
|
Corrections verified for completion, fire life safety finaled.
|