Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-02809 FIRE-Final Inspection4/21/20084/21/20084/21/2008 5:28:14 PMPFAIL
Missing suite address numbers, provide max. occupant load signs per review notes, provide approved door hardware at the balcony/patio doors, missing EM lighting and exit signs at various locations, provide signage at the door the the fire riser room, remove the curtain blocking the SE kitchen exit door, storage at the kitchen areas to remain below 18" from the sprinkler deflector.
FIR07-01045 INSP-Final Inspection4/21/20084/21/20084/21/2008 5:20:40 PMPPASS
Fire alarm testing passed field inspection per K.R. NOTE: As-builts reflecting four additional duct detectors to be provided as agreed.
BLD07-03090 FIRE-Final Inspection4/21/20084/21/20084/21/2008 5:18:55 PMPFAIL
Door hardware is not approved as installed.
FIR08-00127 INSP-Final Inspection4/21/20084/21/20084/21/2008 5:18:11 PMPPASS
Fire alarm testing passed per K.R permit finaled.
FIR08-00267 INSP-Final Inspection4/21/20084/21/20084/21/2008 5:17:06 PMPPASS
Hood suppression system functioned properly under test conditions, permit finaled per K.R.
FIR08-00118 INSP-Final Inspection4/18/20084/21/20084/21/2008 3:03:24 PMPCANC
Inspection rescheduled for 4/22 per discussion.
FIR06-00535 INSP-Final Inspection4/18/20084/21/20084/21/2008 3:02:31 PMPCANC
Rescheduled per conversation with contractor.
BLD07-02764 FIRE-Final Inspection4/21/20084/21/20084/21/2008 2:46:38 PMPFAIL
Storage at the basement level mechanical crawl space is not allowed- need to remove construction materials (paint, carpet, etc. from this area), the provided fire extinguishers are mounted too high and are missing the required current inspection/certification tags-see fire code review notes for stipulations, repair the non-functional EM light at the basement rated stair enclosure, door hardware at the 2nd floor and basement level offices and restrooms must be approved.
BLD08-00440 FIRE-Final Inspection4/18/20084/21/20084/21/2008 1:57:03 PMAFAIL
Exit signs at three locations are not functional on battery backup power, missing approved door hardware at the remodeled rooms and areas.
BLD08-00076 FIRE-Final Inspection4/21/20084/21/20084/21/2008 12:56:21 PMPPASS
Fire life safety inspection passed.
FIR08-00048 INSP-Final Inspection4/18/20084/21/20084/21/2008 12:09:31 PMAPASS
Fire sprinkler permit work passed final inspection.
FIR07-00958 INSP-Final Inspection4/18/20084/21/20084/21/2008 12:05:20 PMAFAIL
Pendent head deflector at a storage closet is cut above the drop ceiling and missing escutcheon, noted the need to maintain 18" clearance to storage below sprinkler heads at the kitchen areas.
BLD08-00161 FIRE-Final Inspection4/17/20084/21/20084/21/2008 12:01:23 PMAPASS
Life safety inspection passed, one duct detector vent tube install corrected while on site.
BLD07-03264 FIRE-Final Inspection4/18/20084/21/20084/21/2008 11:58:55 AMAPASS
Corrections verified for completion, fire life safety finaled.