FIR08-00068
| INSP-Sprinkler Rough-in | 4/21/2008 | 4/21/2008 | 4/22/2008 2:39:25 PM | P | PASS |
|
|
See the city approved plans for new areas above hard lids that are marked ok to cover.
|
FIR08-00066
| INSP-Sprinkler Rough-in | 4/21/2008 | 4/21/2008 | 4/22/2008 1:58:39 PM | P | PASS |
|
|
See the city approved plans for new areas that are marked ok to cover.
|
BLD07-03277
| FIRE-Conference | 4/21/2008 | 4/21/2008 | 4/21/2008 6:05:04 PM | P | FAIL |
|
|
See the city approved plans for deficiancy locations.
|
BLD08-00375
| FIRE-Final Inspection | 4/21/2008 | 4/21/2008 | 4/21/2008 4:18:50 PM | P | FAIL |
|
|
The doors and hardware have not been installed yet. No inspection was performed.
|
BLD08-00537
| FIRE-Final Inspection | 4/21/2008 | 4/21/2008 | 4/21/2008 3:55:01 PM | P | FAIL |
|
|
Provide the annual inspection (certification) for the existing fire alarm panel which currently has red and yellow lights flashing on the remote annunciator. Provide sprinkler protection in the short corridor next to the breakroom. Install the ceiling in the comm. room. Repair the west exit sign. Provide approved drawings on site for the inspectors review.
|
FIR07-00969
| INSP-Sprinkler Rough-in/Hydro | 4/21/2008 | 4/21/2008 | 4/21/2008 3:52:40 PM | P | PASS |
|
|
The underground hydro test and flush passed
|
FIR08-00221
| INSP-Sprinkler Rough-in | 4/17/2008 | 4/21/2008 | 4/21/2008 3:51:53 PM | A | PASS |
|
|
The sprinkler piping rough-in is passed. The insulation needs to be installed over the piping in the new addition and inspected. The tenting needs to be performed over the piping in the existing section and inspected.
|
FIR06-00011
| INSP-Alarm Testing | 4/18/2008 | 4/21/2008 | 4/21/2008 11:51:18 AM | A | FAIL |
|
|
The smoke detector did not operate the sliding window
|
BLD06-00716
| FIRE-Final Inspection | 4/18/2008 | 4/21/2008 | 4/21/2008 11:28:55 AM | A | PASS |
|
|
life safety passed
|
FIR08-00213
| INSP-Sprinkler Rough-in | 4/18/2008 | 4/21/2008 | 4/21/2008 10:47:15 AM | A | PASS |
|
|
The inspection today was just for the armovers/hangers. No T-bar has been installed and the flex heads have not been installed into the grid.
|
FIR08-00211
| INSP-Sprinkler Rough-in | 4/18/2008 | 4/21/2008 | 4/21/2008 10:46:43 AM | A | PASS |
|
|
The inspection today was just for the armovers/hangers. No T-bar has been installed and the flex heads have not been installed into the grid.
|